Manual - TC.P Quadro
TopControl application
2016-08-05
224/330
V04.52
6
1
4
5
6
7
2
3
Fig. 133
<CONFIG> tab
– parameters.
<CONFIG> tab
– parameters
1
Controller,
group
Controller parameters for voltage, current and power control
P-Gain
Proportional term for the gain (constant)
I-Gain
Integrating controller term
D-Gain
Differential controller term
T1
Delay term for the D-gain
Feedfwd
Portion of the input that is forwarded directly to the output.
I-Adaptiv
Additional gain in the lower current range
P-Adaptiv
Additional gain in the lower current range
2
Load rejection,
group
Current difference
1
Control difference value (current here). If the limit value set
is exceeded, the control value is set to Maximum PWM.
Maximum PWM Maximum pulse-width modulation [%] is activated as control-
ler value if the current difference exceeds the limit value
specified.
3
Voltage sensing,
group
For further information on the parameters
see Table 135, page 226
4
Filters,
group
Analog input bandwidth: cut-off frequency for the analogue output filter (actual
values)
Analog output bandwidth: cut-off frequency for the analogue input filter (set
values)
1
If the output current from the power supply drops by more than the threshold given
within 50
μs, the power stage is immediately returned to the % value given for the
actual operation. This feature is useful to avoid voltage rises that are produced on