Manual - TC.P Quadro
D) Configuration
2016-08-05
301/330
V04.52
9
9.1.14.
D) Configuration
Flash
Code
Error
Error message
TopCon (Long)
Description
Possible Cause
Counteraction
14-1
D0
Slave ID or ad-
dress (RSC on) not
unique
Module ID or address of a slave is
identical with the Module ID or ad-
dress (RSC on) of a other slave.
Every slave needs a unique mod-
ule ID or module address (RSC
on).
Make sure that each slave has an unique num-
bered module ID. In operation with the option
TC._RSC needs a Slave a unique module ad-
dress.
14-2
D1
HMI/RCU ID not
unique
The same HMI/RCU ID was as-
signed several times.
Every HMI/RCU needs a unique
HMI ID (HMI identification).
Change the HMI ID in the HMI menu to an unique
HMI ID in the multi-unit system.
14-3
D2
More than one
master in system
More than one divice with module ID
= 0 was detected.
In each system exactly one Top-
Con-Master (identified by module
ID = 0) must exist.
Check the modul ID in all devices.
Only in one device is a modul ID setting ID= 0
allowed.
14-4
D3
Nominal power of a
slave not con-
sistent
Nominal power setting of a devices
does not match to master configura-
tion
The nominal data of all modules in
a network must be identical with
that of the master device.
The nominal data of all modules in a network must
be identical with that of the master device.
14-5
D4
Nominal voltage of
a slave not con-
sistent
Nominal voltage setting of a devices
does not match to master configura-
tion
The nominal data of all modules in
a network must be identical with
that of the master device.
The nominal data of all modules in a network must
be identical with that of the master device.
14-6
D5
Nominal current of
a slave not con-
sistent
Maximal current setting of a devices
does not match to master configura-
tion
The nominal data of all modules in
a network must be identical with
that of the master device.
The nominal data of all modules in a network must
be identical with that of the master device.
14-7
D6
Number of devices
in series config.
does not corre-
spond with the
given value
The number of devices in serial or
parallel circuit does not match with
the system configuration.
The module IDs are badly config-
ured.
Consult manual to reconfigure module IDs to
match the requirements.
14-7
D6
Number of devices
in series config.
does not corre-
spond with the
given value
The number of devices in serial or
parallel circuit does not match with
the system configuration.
default setting differs from the
actual number of modules in serial
or parallel connection.
Connecting the same number of devices as speci-
fied.
Adapt the settings using TopControl to the actual
number of devices.
14-7
D6
Number of devices
in series config.
does not corre-
spond with the
given value
The number of devices in serial
circuit does not match with the sys-
tem configuration.
One slave at minimum was not
detected as a result of a commin-
cation or login error
Cf. 6) and C).