Manual - TC.P Quadro
F) Miscellaneous
2016-08-05
307/330
V04.52
9
Flash
Code
Error
Error message
TopCon (Long)
Description
Possible Cause
Counteraction
16-8
F7
Enable signal mis-
sing
Optional enable signal not present
Optional enable signal function
enabled and:
VoltageOn-try with enable signal
not present or enable signal re-
moved while system is VoltageOn
Check for correct enable signal cabling (may be
attached to pin 8, 18,19, 20 on X105 depending on
configuration)
16-9
F8
External QBottom-
PWM shut-down
Switching off of the QBottom-PWM
was produced by an external signal.
This signal is not wired to the out-
put. Thus only a very strong EMI
interference is able to trigger this
error.
Find the EMI sources e.g. contactors without free
wheeling diodes.
16-11 FA
Any Rack did not
change to voltage-
on or -off within
specified timeout
Error specific to Multi rack controller
(MRC):
The Voltage On/Off command was
not accepted from all TopCon devic-
es connected.
Analogue signal for power ON
input of a TopCon device works
improperly.
Set value for of the debouncing time high-
er.Contact customer support for this.
16-11 FA
Any Rack did not
change to voltage-
on or -off within
specified timeout
Error specific to Multi rack controller
(MRC):
The Voltage On/Off command was
not accepted from all TopCon devic-
es connected.
Cabling not correct.
Check the cabling.
16-12 FB
Any Rack system
has errors, or
dummy plug miss-
ing
Error specific to Multi rack controller
(MRC)
Error occurred in one of the Top-
Con devices.
See in error description of the corresponding
TopCon device
16-12 FB
Any Rack system
has errors, or
dummy plug miss-
ing
Error specific to Multi rack controller
(MRC)
Dummy plug on MRC is missing.
Ensure that unused ports of the MRC are covered
by dummy plug.
16-13 FC
ReGen error
Error in an optional external energy
feedback unit. Applies as well to
ResAct systems.
See separate documentation of
the ReGen / ResAct system.
See separate documentation of the ReGen /
ResAct system.