Manual - TC.P Quadro
U) Configuration 3
2016-08-05
324/330
V04.52
9
Flash
Code
Error
Error message
TopCon (Long)
Description
Possible Cause
Counteraction
29-5
U4
Nominal current of Sub-Systems not
consistent
Maximum current not
identical on all Sub-
Systems
Different number of serial devices in a
Sub-System.
29-5
U4
Nominal current of Sub-Systems not
consistent
Maximum current not
identical on all Sub-
Systems
Different maximum current values in
the devices of the Sub-Systems.
29-6
U5
One or more Sub-System(s) are miss-
ing
The detected number of
Sub-Systems
in a total system are
lower than configured.
Error while Subsystem login or config-
uration.
29-6
U5
One or more Sub-System(s) are miss-
ing
The detected number of
Sub-Systems
in a total system are
lower than configured.
Wrong MAC bus wiring.
29-6
U5
One or more Sub-System(s) are miss-
ing
The detected number of
Sub-Systems
in a total system are
lower than configured.
Wrong TC.MAC configuration.
29-7
U6
One or more Sub-System(s) with inva-
lid ID or address (RSC on)
One or more Sub-
System ID's or address-
es (RSC on) are outside
valid range
ID AH and AL are exchanged
ID AH or AL value too large
See TC.MAC manual
29-8
U7
Total number of Sub-Systems does not
match with configuration
Total number of Sub-
Systems does not match
with the configuration of
a total system
Subsequent error of error U5) or U6)