Manual - TC.P Quadro
Technical data
2016-08-05
38/330
V04.52
3
3.1.6.
Ambient conditions
Ambient conditions for standard devices
1
Maximum ambient tem-
perature
Storage temperature
-25
– 70 ˚C
Cooling air temperature
in operation
5
– 40 ˚C
Ventilation type
Standard
Forced ventilation and temperature-
controlled
Liquid cooled (LC)
(option)
(Partially) liquid cooled
(see chapter 4.2.1, page 91)
Atmospheric humidity
15
– 85 %, non-condensing
Installation altitude
0
– 1000 m above sea level
Nominal power operation
Max. 1000 m above sea level
Reduced power
Max. 2000 m above sea level
Ingress protection (IEC
60529)
Basic version
IP 20
Appropriate
case
2
Up to IP 43
Utilisation category
Protection class
I
Overvoltage category
I I I
Degree of soiling
2
Vibration
2
Up to 2 g
Table 23
1
For versions with expanded characteristics, please contact your
TopCon sales partner.
2
Tested in accordance with standard IEC 60068-2-6.
3.1.7.
Interfaces (standard)
In the following the interfaces that are included with a power supply in
the TopCon Quadro series are briefly described.
As an option the power supplies can be manufactured with numerous
additional interfaces. (See chapter 4.4, from page 122)