Flashing code sequence with errors or warnings
1. Error codes and warning codes are identical.
All errors and warnings are output one after the other based on
the scheme in Fig. 37, page 82.
2. After the output of the last error or warning the flashing se-
quence starts again with the first error or first warning.
The list of all errors and possible rectification measures is given in the
appendix.
For information on the rectification of errors using the error list see
chapter 9.1, page 264.
Practical example
After switching on the TopCon Quadro power supply and setting the set
values, the device is activated (On/Off). The buzzer comes on and an
error code is indicated via the light emitting diodes:
Count the flashes:
Group error code = 16,
Detail error code = 3.
Reference to the error code list shows that an interlock error has been
detected (F-2).
Note that the error coding is in hexadecimal. F
Hex
= 15
10
, 3 is the third
element in 0, 1, 2, 3....
The indication on the HMI or in TopControl is: 0… 15 or 0 …F
Hex
.
The flashing code on the “ERROR” LED does not have a zero and
therefore assumes the counting order 1…16. 0 signifies a pause in the
flashing.
3.3.6.8. Acknowledging an error
After the occurrence of an error, the device remains in the ERROR
state until the reason for the error has been rectified (as per error list)
and the error has been acknowledged.
It is possible to acknowledge an error via the following interfaces:
HMI
Using the
<ESC>
button on the front of the device
TopControl
Using the
<Clear error>
button on the
<CONTROL>
tab
Analogue interface X105
Positive edge on pin 8 with 10-24 V relative to ground