4.2.1.4. Filling cooling liquid circuit
By using this procedure you will reduce the formation of bubbles in the
cooling system.
1. Only fill the cooling liquid circuit from one end via a cooling liquid
connection.
2. Fill the system until the cooling liquid flows out of the other con-
nection.
The formation of bubble in the cooling circuit is minimised.
3. Connect the device to your cooling circuit.
3
1
2
Fig. 44
Examples for liquid cooling using cooling liquid:
90 ° quick-release isolating valves
-1-
on a 32 kW power supply
Hosing
-2-
and pipework
-3-
on a 32 kW power supply in a device
cabinet.