Manual - TC.P Quadro
C) Login
2016-08-05
296/330
V04.52
9
9.1.13.
C) Login
Flash
Code
Error
Error message
TopCon (Long)
Description
Possible Cause
Counteraction
13-1
C0
Slave did not re-
ceive CFL
The slave has not received a request
to log on to the system. These errors
cannot be detected by the master.
They only occur at the corresponding
slaves.
No master has been defined.
You have to assure that a master (module ID=0)
is available.
13-1
C0
Slave did not re-
ceive CFL
The slave has not received a request
to log on to the system. These errors
cannot be detected by the master.
They only occur at the corresponding
slaves.
Master device is switched on be-
fore the slave has been switched
on.
Switch on the master always after all slaves, but
within a 10 seconds period.
13-1
C0
Slave did not re-
ceive CFL
The slave has not received a request
to log on to the system. These errors
cannot be detected by the master.
They only occur at the corresponding
slaves.
Master device is not switched
before the end of the 10s slave
timeout.
Switch on the master always after all slaves, but
within a 10 seconds period.
13-1
C0
Slave did not re-
ceive CFL
The slave has not received a request
to log on to the system. These errors
cannot be detected by the master.
They only occur at the corresponding
slaves.
Cable between master and slave
not properly connected.
Check proper mounting of cable.
13-1
C0
Slave did not re-
ceive CFL
The slave has not received a request
to log on to the system. These errors
cannot be detected by the master.
They only occur at the corresponding
slaves.
The controller board has no sup-
ply voltage. (LED's remain dark
when switching on).
In the case of repeated occurrence refer to cus-
tomer support .
13-1
C0
Slave did not re-
ceive CFL
The slave has not received a request
to log on to the system. These errors
cannot be detected by the master.
They only occur at the corresponding
slaves.
Master and Slave(s) do not use
the same CAN Baudrate
Contact customer support