Electrical connections
3.2.4.1. Electrical installation
– general
In the following basic requirements on the electrical installation of elec-
trical power supplies with TopCon power supplies are described.
General information on installation
Prior to installation and commissioning, these operating instructions as
well as any other information and instructions are to be read carefully.
Possible mortal danger due to electric shock!
Due to tampering with electrical modules
Avoidance:
The electrical installation is to be undertaken by personnel
with electrical training.
Never connect or disconnect electrical connections while they
are live.
The correlation of the modules and documentation supplied must be
checked:
1. Do the type plates match the order and delivery
documentation?
2. Are the device nominal data suitable for the intended
application?
3. Do the cables/connector supplied match the intended
connections?
During the installation work, pay particular attention to the following:
1. Never connect or disconnect electrical connections while they
are live!
2. Lay cables carrying high currents using an adequate cable
cross-section as per VDE0110!
3. Ensure correct earthing of each power supply to a common
PE rail!
4. It is imperative cable shields are connected via the cable clamps
and/or connector cases to earth or the case on the power sup-
plies using large area connections!
5. Follow measures for compliance with EMC regulations in the fol-
lowing section on electromagnetic compatibility page 50.
6. Provide safety shutdown feature (EMERGENCY STOP/interlock)
and test it!
WARNING