Manual - TC.P Quadro
Control
2016-08-05
80/330
V04.52
3
3.3.6.2. Indications on DEVICE and CONTROL LEDs
State of the device
DEVICE and CONTROL LEDs on the front of the
device
“READY”
“STATUS” “ERROR”
“CV”; ”CC”
and “CP”
Power UP
OFF
ON
OFF
OFF
STOP
ON
ON
OFF
OFF
READY
ON
FLASH-
ING
3)
OFF
OFF
RUN
ON
1)
OFF
OFF
ON
2)
warn
ON
1)
FLASHING
3)
OFF
ON
2)
Error
ON
OFF
4)
FLASHING
3)
OFF
FATAL ERROR
5)
FLASH-
ING
5)
FLASH-
ING
5)
FLASH-
ING
5)
OFF
Table 48
Indication of the system status via LED indication (front).
1
Flashing, if a discharge device is active.
2
One of the three LEDs, as per the actual control mode.
3
Flashing code as per the error table or warning table
(see chapter on troubleshooting).
4
Flashing, if a warning is active at the same time.
5
The three LEDs are flashing together: internal communication failed.
Description of the shutdown process
On devices with 20 kW and 32 kW:
Changing the position of the main switch does not shut down the Top-
Con power supply immediately, instead a shutdown process is initiated.
In particular, the discharge of the internal capacitors takes a certain
amount of time during which the device is still live internally and to
some extent the outputs are still live.
As long as the shutdown process is running:
The three DEVICE LEDs form a running light.
The HMI display indicates “shutting down…”
For this reason it imperative to wait until this process is complete before
undertaking further tasks on the device.
On devices with 10 and 16 kW the shutdown process is so fast that
there is no indication and no delays.