4.2.1.2. Characteristics of a water cooling circuit
General information on the heat exchanger
Label
TC.P.10
TC.P.16
TC.P.20
TC.P.32
Connections
On rear side of device, G 1/2“
Cooling medium (KM)
Purified water, alternatively heat
exchanger liquids, non-corrosive
Heat sink material
EN AW-5083
KM
1
specific heat capacity
4.19 kJ/kgK
Thermal rating
0.8 kW
1.3 kW
1.5 kW
2.0 kW
R
th
(KM-Case)
Approx. thermal resistance
of the cooling device
< 0.01 K/W
Recommended flow rate KM
4
– 7 l/min
Minimum KM flow rate
for dT
10 K,
dT
≙
temp. difference between
inlet and outlet temp. of the cool-
ing liquid.
2.0 l/min
2.5 l/min
Maximum permissible continuous
outlet temperature KM
2
40 °C@ 2.5 l/min
50 °C@ 5 l/min
Maximum permissible
inlet temperature KM
2
25 °C@
≥ 2.5 l/min
40 °C@ 5 l/min
Table 56
Characteristics of the liquid cooling.
1
On the usage of cooling liquids with significantly different specific
heat capacity the figures must be modified accordingly!
2
For other temperature values, please contact
Regatron support.
Damage due to condensation!
Damage in the device due to condensed water is excluded from the
warranty.
Reason:
Due to cooling liquid temperatures < 15 °C.
In case of an ambient temperature of 20 °C
and relative atmospheric humidity of
≥ 70 %.
Avoidance:
Keep the feed temperature at a temperature level > 15 °C to
avoid condensation inside the device and on the supply ca-
ble.
In case of doubt contact Regatron support.