Manual - TC.P Quadro
Hardware options
2016-08-05
95/330
V04.52
4
Possible damage!
Deionised water will result in corrosion.
Avoidance:
Avoid deionised water completely.
4.2.1.3. Pressure difference/flow rates
The maximum permissible cooling liquid pressure is 4 bar = 4000 hPa.
Standard connection with G ½“
Heat sink with internal pipework, ready for connection of cooling liquid
on site at the rear side of the device:
Pressure difference
Flow rate valve
1
with G 1/2 ‘‘
0.02 bar
2.5 l/min.
0.04 bar
3.5 l/min.
0.07 bar
1
5 l/min.
2
0.12 bar
7 l/min.
Table 58
List of pressure difference vs. flow rate.
1
The maximum permissible cooling liquid pressure is 4 bar = 4000 hPa.
2
Recommended range
Connection with quick-release isolating valves
Heat sink with internal pipework, ready for connection of cooling liquid
on site at the rear side of the device plus 2 quick-release isolating
valves (on customer request), inside diameter = 6 mm:
Pressure difference
Flow rate quick-release isolating valves
0.06 bar
2.5 l/min.
0.15 bar
3.5 l/min.
0.24 bar
1
4.5 l/min.
1
0.38 bar
1
6 l/min.
1
0.48 bar
7 l/min.
Table 59
List of pressure difference vs. flow rate with additional quick-release connection.
1
Recommended range
The pressure drops for on-site feed pipes, manifolds and pressure and
flow rate sensors are also to be taken into account. In particular, on the
parallel supply of several power supplies an appropriate safety margin
is to be included.
CAUTION