Manual –TC.GXS
2016-09-16
22 / 43
Template V02.11
General notices
•
It is imperative to remove all cable connections prior to moving
the system!
•
Note that between switching off the power supply device and
disconnecting the power cables on the output side, it is
necessary to wait at least 15 min for discharging.
•
Keep all doors closed during the transport of switch cabinets.
•
Pay attention to protruding parts such as main switch, controls
and fan covers. They must not be damaged by transport aids
(straps, blocks of wood, etc.).
•
Do not transport the switch cabinet laying flat, to avoid transport
damages.
2.7. Area related to interaction with the system
Compliance with the design data for the specific system is a
prerequisite for malfunction-free operation.
Load systems can have significant effects on the power source.
The following points are to be noted:
1. The maximum voltage specified is not allowed to be
exceeded.
2. Protective measures must be provided against voltage spikes
on the load side and their function must be monitored
(voltage spikes could damage the filter capacitors and
semiconductors in the system).
3. Periodic overcurrents are to be avoided.
4. The DC ripple currents produced on the load side are to be
monitored to avoid overloading filter capacitors; in case of
doubt ask the manufacturer.
5. The system is always to be operated within the permissible
temperature range. High temperatures will significantly
reduce the service life of various components.