5.2.3.
Electromagnetic compatibility/interference suppression
TopCon systems are equipped with interference protection and
suppression filters in all power and signal connections. On correct
installation, conformity with the applicable standards will be achieved.
Prerequisites for EMI protection:
•
Large surface area earthing (suitable for EMI) of the protection
components.
•
Screening of mains and load connections and earthing of
screens at both ends.
Prerequisites for immunity from interference:
•
Control cables screened and screens earthed at both ends.
•
Star topology earthing (suitable for EMI) of the device.
•
Screen connectors that are earthed directly via earthed sockets
on the electrical power supply.
5.2.4.
System mains connection
Possible injury and damage!
•
Injury due to missing or incorrect PE connection.
Avoidance:
⇒
On completion of connection work, check the cables
connected for firm fixing.
⇒
The mains connection is made:
On systems via the terminals L1, L2, L3, PE.
Please note the following points:
•
For installation location and order of the terminals,
refer to the TC.GSS manual.
•
The system must be electrically isolated and secured against
switching back on.
•
The mains supply cable must have an adequate cable cross-
section. Pay attention to the nominal current information on the
type plate.