12
|
LRI3E-1 / HRI3E-1 Direct Vent Gas Insert
|
12
installation
Diagram 1
Diagram3
Diagram 2
Note: A 3-1/2" mantel deflector to reduce
mantel height to 28" from bottom of
unit @ 1"depth.
MINIMUM CLEARANCES TO COMBUSTIBLES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this
decorative gas appliance be installed only in accordance with these instructions.
Clearance:
Dimension
Measured From:
A: Sides
6" / 152 mm
From inside edge of faceplate / doors
B: Ceiling
60" / 1524 mm
From Base of Unit
C: Mantel (Min. Height)
*
28" / 711mm
38"/ 965mm
From Base of Unit
From Base of Unit
D:Min. Hearth Depth
12" / 305mm
Not required if unit raised 3-1/2" off floor
E: Min. Hearth Length
36"/ 914mm
G: Max. Mantle Depth
0
-
12" / 305 mm
@ 47" (1193mm) from bottom of unit
without deflector @12" (305mm) deep
@ 37" (940mm) from bottom of unit with
3-1/2" deflector @12" (305mm) deep
K: Min. Alcove Width
54" / 1372 mm
L: Max. Alcove Depth
36" / 914 mm
M: Mantel Deflector
3-1/2"/ 89mm
NOTE: 36” (914 mm) wide x 12” (305mm) deep non combustible hearth is required in front
of the appliance, unless the unit is raised 3-1/2” (89 mm) off the floor surface.
*An optional 3-1/2" deflector, reduces the mantel height to 28" from bottom of unit
@ 1"depth.
A
C
B
E
K
D
L
G
Mantel Clearances
2
0
12
6
4
8
10
0
24
12
16
20
12" (305mm)
1" (25mm)
19" (483mm)
19"(483mm)
to base of unit
Side View
32
28
4
8
28" (711mm)
Top of fireplace
opening
Non Combustible
Mantel Clearances
2
0
12
6
4
8
10
0
24
12
16
20
12" (305mm)
1" (25mm)
9" (229mm)
19"(483mm)
to base of unit
Side View
32
28
Non Combustible
4
8
18" (457mm)
Deflector
Top of fireplace
opening
MANTEL CLEARANCES WITHOUT DEFLECTOR
MANTEL CLEARANCES WITH 3-1/2" DEFLECTOR
WARNING
Although this appliance passes safety
certification, the hearth in front of the fireplace
becomes very hot when the fireplace heats. Do
not use the hearth as a seat or shelf.
A noncombustible mantel may be
installed at a lower height
if the framing is made of
metal studs covered with a
noncombustible board.
Note: All material used must be
completely non-combustible.