10
Regency U28-2/U43-3 ULTIMATE Freestanding Gas Stove
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas
supply piping system by closing its individual
manual shut-off valve during any pressure
testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig. (3.45
kPa). Disconnect piping from valve at pressures
over 1/2 psig (14" w.c.).
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure,
both inlet and manifold pressures
should be checked using the valve
pressure ports on the valve.
INSTALLATION
For 0 to 2000 feet altitude
Burner Inlet Orifice Sizes:
Natural Gas Propane
Burner #32
#50
Max. Input
- Natural Gas/Propane
38,000
Btu/h
Min. Input
- Natural Gas/Propane
20,000
Btu/h
Output Capacity with blower Off
Natural Gas
27,740 Btu/h
Propane
28,200 Btu/h
Output Capacity with blower On
Natural Gas
29,260 Btu/h
Propane
29,640 Btu/h
Supply Pressure
Natural Gas
min. 5" w.c.
Propane
min. 12" w.c.
Manifold Pressure
Natural Gas
3.8" +/- 0.2" w.c.
Propane
11" +/- 0.2" w.c.
Electrical: 120 V. 1.13A 60Hz.
Circulation: Variable speed fan, 125/75 CFM.
Log Set: Ceramic fiber, 3 per set.
System Data:
HIGH ELEVATION - U43-NG3
For 2,000 - 4,500 feet altitude
Burner Inlet Orifice Sizes:
Natural Gas
Burner #33
Max. Input Rating
34,000 Btu/h
Min. Input Rating
18,000 Btu/h
Output Capacity with blower Off
Natural Gas
24,820 Btu/h
Max. Output Capacity with blower On
Natural Gas
26,180 Btu/h
System Data
U43-NG3 & U43-LP3
GAS CONNECTION
The gas line can be rigid pipe, or to make installation easier, use a listed flexible connector if
allowed by local codes. Copper may also be used if approved by local codes.
The gas connection at the valve is 3/8" NPT. For minimum and maximum supply pressure see
the System Data Table.
Vent Terminations
Installation into Existing
Woodstove Flue System
1)
Clean existing Chimney system.
2)
Run an approved 4" flex liner or "B" vent
into existing chimney.
Note: See the chimney systems manu-
facturer for detailed installation
instructions.
System Data
U28-NG2 & U28-LP2
For 0 to 4500 feet altitude
Burner Inlet Orifice Sizes:
Natural Gas Propane
Burner #40
#53
Max. Input
- Natural Gas/Propane
27,000 Btu/h
Min. Input
- Natural Gas/Propane
13,500 Btu/h
Output Capacity with blower Off
Natural Gas
19,305 Btu/h
Propane
19,440 Btu/h
Output Capacity with blower On
Natural Gas
20,142 Btu/h
Propane
20,250 Btu/h
Supply Pressure
Natural Gas
min. 5" w.c.
Propane
min. 12" w.c.
Manifold Pressure
Natural Gas
3.8" +/- 0.2" w.c.
Propane
11" +/- 0.2" w.c.
Electrical: 120 V. 1.13A 60Hz.
Circulation: Variable speed fan, 125/75 CFM.
Log Set: Ceramic fiber, 3 per set.