Regency U28-2/U43-3 ULTIMATE Freestanding Gas Stove
TEST FOR FLUE
SPILLAGE
A "spillage" test must be made before the
installed unit is left with the customer. Follow
the procedure below:
1)
Start all exhaust fans in the home and any
other gas appliances. Then close all doors
and windows.
2)
Light the unit and set controls to maximum.
3)
After five minutes, test that there is a "pull"
on the flue by placing a smoke match,
cigarette or similar device which gives off
smoke, on the edge of the draft hood. See
diagrams.
The thermally activated safety
switch must be manually reset
before first startup.
U28: LOUVER
INSTALLATION
1)
Attach the top & bottom louvers to the side
stove panel using 2 screws per side.
Diagram 1
FRONT DOOR
INSTALLATION
(packaged separately)
1)
Open the two side panels.
2)
Slide the door onto the two hinge pins making
sure the two pieces are flush together. See
diagram 1.
3)
Close the door. The latch plate must be
centered around the alignment pin. See
diagram 2. If the latch plate interferes with
the corner of the stove you may want to
angle the plate slightly so the door closes
easier.
4)
The latches should already be at the proper
setting. If they are too hard or too easy
to close, you may want to adjust them by
loosening the latch catch. See diagram 3.
Diagram 2 - U43
Diagram 3 - U43
Diagram 2 - U28
Diagram 3 - U28
INSTALLATION
5)
Remove the blue plastic protective coating
from the glass.
6)
Test the seal around the door by placing
a piece of paper between the unit and the
door, close the door and try to pull the paper
out. If it slips out easily, then the door is not
properly sealed. Tighten or loosen the latch.
See diagram 3.
Note: The door latch may require adjust-
ment as the door gasket material
compresses after a few fires and
after glass replacement. Turn the
latch catch inward or outward to
loosen or tighten.
The smoke should
be drawn into the
draft hood. If the
smoke is not drawn
into the draft hood,
turn the unit off and
check for the cause
of lack of draft.
Note: If the flue is blocked or has a strong
reverse flow, the thermally actuated safety
switch mounted in the draft hood will auto-
matically shut off the gas supply within about
10 minutes. If the heater turns off because
of this during the spillage test, check for the
cause of the lack of draft.