10
Regency Bellavista™ B41XTCE Gas Fireplace
INSTALLATION
Caution Requirements
The top, back and sides of the fi replace are defi ned by
standoffs. The metal ends of the standoff may
NOT
be
recessed into combustible construction.
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this
fi
replace and vent
system be installed only in accordance with these instructions.
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related
fi
res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest
importance that this
fi
replace and vent system be installed only in accordance with these instructions.
B41XTCE Clearance Requirements
Horizontal Top
3" (76mm)
Horizontal Side
2 " (51mm)
Horizontal Bottom
2" (51mm)
Vertical Vent
2" (51mm)
NOTE:
A 16" deep non-combustible hearth pad is
recommended for hardwood fl ooring and carpet.
Clearance:
Dimension
Measured From:
A: Mantel Height (min.)
17-9/16" (446mm)
Top of Fireplace Opening
B: Sidewall
9" (229mm)
Side of Fireplace Opening
C: Ceiling
36-5/8" (930mm)
Top of Fireplace Opening
D: Mantel Depth (max.)
12" (304mm)
25-13/16" (651mm)
from Top of Fireplace Opening
E: Alcove Width
60" (1524mm)
Wall to Wall (Minimum)
F: Alcove Depth
36" (914mm)
Front to Back Wall (Maximum)
Notes:
0"
No Hearth Required
Minimum Vent Clearances
to Combustibles
Alcove
E
F
C
D
A
E
F
C
Close to Ceiling
F
E