20
Regency Bellavista™ B41XTCE Gas Fireplace
INSTALLATION
EXTERIOR VENT TERMINATION REQUIREMENTS
Minimum Clearance Requirements
Canada
1
USA
2
A
Clearance above grade, veranda, porch, deck, or balcony
12"(30cm)
12"(30cm)
B
Clearance to window or door that may be opened
12"(30cm)
9" (23cm)
C
Clearance to permanently closed window
*
*
D
Vertical clearance to ventilated sof
fi
t located above the terminal within a horizontal distance of 2 feet (61cm)
from the center line of the terminal (check with the local code)
24"(60cm)
24"(60cm)
E
Clearance to unventilated sof
fi
t
19-1/2"(50cm)
20"(51cm)
F
Clearance to outside corner: with AstroCap XL Termination Cap.
13"(33cm)
13"(33cm)
Clearance to outside corner: with all other approved Termination Caps.
13"(33cm)
13"(33cm)
G
Clearance to inside corner: with AstroCap XL Termination Cap
5-1/2"(14cm)
5-1/2"(14cm)
Clearance to inside corner: with all other approved Termination Caps.
7"(18cm)
7"(18cm)
H
Clearance to each side of center line extended above meter/regulator assembly
36"(90cm)
a
*
J
Clearance to service regulator vent outlet
36"(90cm)
*
K
Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance
12"(30cm)
9" (23cm)
L
Clearance to a mechanical air supply inlet #3' (91cm) above if within 10' (3m) horizontally.
72"(1.8m)
36"(90cm)
b
M
Clearance above paved sidewalk or a paved driveway located on public property
84"(2.1m)
┼
*
N
Clearance under veranda, porch, deck, or balcony
12"(30cm)
‡
*
1
In accordance with current CSA B149.1,
Natural Gas and Propane Installation Code
2
In accordance with the current
ANSI Z223.1/NFPA 54, National Fuel Gas Code
┼
A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings
‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the
fl
oor
* Clearance in accordance with local installation codes and the requirements of the gas supplier
a
3 feet (91cm) within a height of 15 feet (4.5m) above the meter / regulator assembly
b
3 feet (91cm) above - if within 10 feet (3m) horizontally