City Series ACB60E
|
57
installation
Horizontal Terminations - Rigid Pipe 127 mm x 203 mm
The minimum components required for a basic horizontal
termination are:
1 Horizontal Termination Cap
1 Rigid Pipe Adaptor (770-994)
1 Wall Thimble
1 Length of pipe to suit wall thickness
(see chart)
Wall thickness is measured from the back standoffs to the inside
mounting surface of termination cap. For siding other than vinyl
furring strips may be used, instead of the vinyl siding standoff, to
create a level surface to mount the vent terminal. The Terminal
must not be recessed into siding. Measure the wall thickness
including furring strips.
If a Vinyl Siding Standoff is required (it must be used with vinyl
siding), measure to outside surface of wall without siding and
add 51 mm.
When using Rigid Vent other than
Simpson Dura-Vent, 3 screws must be
used to secure rigid pipe to adaptor.
WARNING:
Do not combine venting components from
different venting systems.
However use of the the AstroCap
TM
and FPI
Riser is acceptable with all systems.
Flat Wall Installation
Wall Thickness
Vent Length Required
102 mm - 140 mm
152 mm
178 mm - 216 mm
229 mm
246 mm - 292 mm
305 mm
229 mm - 368 mm
279 mm - 371 mm Adj. Pipe
381 mm - 597 mm
432 mm - 610 mm Adj. Pipe
Pipe Length
Vertical Terminal
Storm Collar
Flashing
Ceiling Firestop
Adj.Pipe Length
Horizontal
Termination Cap
Wall Thimble
Vinyl Siding
Standoff (Optional)
Rigid Pipe Adapter
o
90 Elbow
Pipe Length
*Unit is not exactly as shown.