8 | I1205
8 |
installation
Clearance diagram for installations
Side and Top facing is a maximum of 1.5" thick.
Floor protection must non-combustible, insulative
material with an R value of 1.1 or greater.
*
If the hearth extension is flush with the floor (F)
it must extend 19.5" in front of the body face
(E).
Note: Hearth Extension Width (G) is measured
from edge of fuel door to side of hearth.
** A non-combustible mantel may be installed
at a lower height if the framing is made of
metal studs covered with a non-combustible
board.
MASONRY AND FACTORY BUILT FIREPLACE CLEARANCES
The minimum required clearances to combustible materials when installed into a masonry or factory built fireplace are listed below.
H
HOW TO DETERMINE IF ALTERNATE
FLOOR PROTECTION MATERIALS ARE ACCEPTABLE
The specified floor protector should be 3/8"
(18mm) thick material with a K - factor of
0.84.
The proposed alternative is 4" (100mm) brick
with a C-factor of 1.25 over 1/8" (3mm) mineral
board with a K-factor of 0.29.
Step (a):
Use formula above to convert specification
to R-value.
R = 1/k x T = 1/0.84 x .75 = 0.893.
Step (b):
Calculate R of proposed system.
4" brick of C = 1.25, therefore
Rbrick = 1/C = 1/1.25 = 0.80
1/8" mineral board of k = 0.29, therefore
Rmin.bd. = 1/0.29 x 0.125 = 0.431
Total R = Rmineral board =
0.8 + 0.431 = 1.231.
Step (c):
Compare proposed system R of 1.231 to
specified R of 0.893. Since proposed system
R is greater than required, the system is
acceptable.
DEFINITIONS
Thermal Conductance:
C
= Btu
= W
(hr)(ft
2
)(
o
F) (m
2)
)(K)
Thermal Conductivity:
k = (Btu)(inch) = W = Btu
(hr)(ft
3
)(
o
F) (m)(K) (hr)(ft)(
o
F)
Thermal Resistance:
R = (ft
2
)(hr)(
o
F) = (m
2
)(K)
Btu
W
Floor Protection
Please check to ensure that your floor protection and hearth will meet the standards for
clearance to combustibles. Your hearth extension must be made from a non-combustible
material.
Thermal floor protection is not required if the unit is
raised 3.5" minimum (measured from the bottom of
the stove). However, standard ember floor protection
is required. It will need to be a non-combustible mate-
rial that covers 16" (406 mm) in the US and 18" (450
mm) in Canada to the front of the unit and 8" (200
mm) to the sides.
If the unit is not raised, thermal floor protection required
is 18" (450 mm) in the US and Canada.
Unit
Adjacent
Side Wall
(to Side)
A
Mantle **
(to Top)
B
Top
Facing
(to Top of Unit)
C
Side
Facing
(to Side of Unit)
D
Minimum
Hearth
Extension*
E
Minimum
Hearth
Thickness
F
Minimum
Hearth Side
Extension*
G
From Top of
Unit
H
I1205S
15" (381mm)
20" (508mm)
14" (356mm)
7-3/8"(187mm)
16" (406mm)
1.5" (38mm)
8" (203mm)
18-3/4"(476mm)
Summary of Contents for Classic I1205M
Page 25: ...Encastrable au bois Regency I1200 25 notes ...
Page 30: ...30 Encastrable au bois Regency I1200 garantie ...
Page 31: ...Encastrable au bois Regency I1200 31 ...
Page 60: ...28 I1205 28 warranty ...
Page 61: ...I1205 29 29 notes ...
Page 62: ...30 I1205 30 notes ...
Page 63: ...I1205 31 31 ...