E18 Gas Insert

MINIMUM FIREPLACE CLEARANCES TO COMBUSTIBLES

Diagram shows the minimum clearances to any combustible material. Installer must check that all installs maintain at least these clearances..

 

32"

813mm

 

 

36"

914mm

 

  37 1/2"

953mm

 

 

21"

533mm

 

  18 5/16"

465mm

 

  11 1/4"

286mm

 

  6 1/4"

159mm

 

  3 3/4"

95mm

 

  7 1/16"

180mm

 

  42 3/4"

1086mm

 

  3 9/16"

91mm

 

  3 1/2"

89mm

 

The minimum clearance from the side of the appliance to a combustible 

side wall is 6" (229mm). The minimum clearance from the bottom edge 

of the front trim above the window to a combustible mantel is 

17- 7/8 "

(454 mm)

. The minimum height from bottom edge of the front trim above 

the window to the ceiling is 

37-7/8"(962 mm). 

Note:  A non-combustible mantel and framing may be installed 

at a closer tolerance if the framing is made of metal studs 
covered with a non-combustible board.

6"

153mm

Min

37 1/2"

952mm

min

17 7/8"

453mm

Min

37 7/8"

961mm

Min

Sidewall

Mantel

Ceiling

Floor

45deg

9"

229mm

Max

 

29"

737mm

 

Allowable 

Mantle

area