Regency F33-1 Freestanding Gas Stove
9
1)
Gas cock knob
2)
Manual high/low adjustment
3)
Pilot Adjustment
4)
Thermocouple Connection
5)
Main Operator
6)
Outlet Pressure Tap
7)
Inlet Pressure Tap
8)
Pilot Outlet
VALVE DESCRIPTION
9)
Main Gas Outlet
10)
Flange Securing Screw Holes
11)
Alternative TC Connection Point
12)
Thermoelectric Unit
13)
Additional Valve Mounting Hole
INSTALLATION
SYSTEM DATA
NG
LPG
Injector size
# 36
# 52
Input Rating
33 mj
33 mj
Manifold Pressure
0.8 kPa
2.38 kPa
GAS PIPE PRESSURE TESTING
The appliance must be isolated from the gas supply piping
system by closing its individual manual shut-off valve during any
pressure testing of the gas supply piping system at test pres-
sures equal to or less than 3.45 kPa. Disconnect piping from
valve at pressures over 3.45 kPa.
The manifold pressure is controlled by a regulator built into the
gas control, and should be checked at the pressure test point.
Note:
To properly check gas pressure, both inlet and
manifold pressures should be checked using the
valve pressure ports on the valve.
1)
Make sure the valve is in the "OFF" position.
2)
Loosen the "IN" and/or "OUT" pressure tap(s), turning
counterclockwise with a 1/8" wide flat screwdriver.
3)
Attach manometer to "IN" and/or "OUT" pressure tap(s)
using a 5/16" ID hose.
GAS CONNECTION
The gas connection is a 1/2 inch BSP Male thread. The gas
line can be rigid copper pipe. Pipe size to ensure correct
operating pressure. For minimum and maximum supply
pressure see the System Data table below.
Note:
During any pressure testing of the gas supply
piping system that exceeds test pressures of 3.45
kPa, this appliance and its individual shut-off valve
must be disconnected from the piping system. If
test pressures equal to or less than 3.45 kPa are
used then this appliance can be isolated from the
piping system by closing its individual manual
shut-off valve, if fitted, during the testing.
INSTALLATION IS TO BE CARRIED OUT
ONLY BY AN AUTHORISED PERSON
4)
Light the pilot and turn the valve to "ON" position.
5)
The pressure check should be carried out with the unit
burning and the setting should be within the limits specified
on the safety label.
6)
When finished reading manometer, turn off the gas valve,
disconnect the hose and tighten the screw (clockwise) with
a 1/8" flat screwdriver.
Screw should be snug, but do not over
tighten.