Regency FG39-1 FireGenie Freestanding Gas Stove
17
INSTALLATION
GAS CONNECTION
The gas line should be rigid pipe. Copper may
also be used if approved by AS5601-2004.
The gas connection at the valve is 1/2 male.
For minimum and maximum supply pressure
see the System Data Table.
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas
supply piping system by closing its individual
manual shut-off valve during any pressure
testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig. (3.45
kPa). Disconnect piping from valve at pressures
over 3.45 kPa (14" w.c.).
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure,
both inlet and manifold pressures
should be checked using the valve
pressure ports on the valve.
1)
Make sure the valve is in the "OFF" posi
-
tion.
2)
Loosen the "IN" (# 3) and/or "OUT" (# 4)
pressure tap(s), turning counterclockwise
with a 1/8" (3mm) wide flat screwdriver.
3)
Attach manometer to "IN" and/or "OUT"
pressure tap(s) using a 5/16" (8mm) ID
hose.
4)
Seal and or check the pilot outlet (# 8)
5)
The pressure check should be carried out
with the unit burning and the setting should
be within the limits specified on the safety
label.
6)
When finished reading manometer, turn
off the gas valve, disconnect the hose and
tighten the screw (clockwise) with a 1/8"
(3mm) flat screwdriver.
Screw should be
snug, but do not over tighten.
AERATION
ADJUSTMENT
The burner aeration is factory set but may need
adjusting due to either the local gas supply or
altitude.
FG39 with 40 mj.
FG39-NG1
Fully Open
FG39-LPG1 Fully Open
FG39 with 31 mj.
FG39-NG1
6 mm Open
FG39-LPG1 10 mm Open
Caution: Carbon will be produced if the air
shutter is closed too much.
Note: Any damage due to carboning result-
ing from improperly setting the aera-
tion controls is NOT covered under
warranty.
Burner Inlet Orifice Sizes:
NG
LPG
Burner #32
#50
2.95mm 1.78mm
Max. Input
NG
40 Mj/h
LPG
38 Mj/h
Min. Input
NG
20 Mj/h
LPG
19 Mj/h
Supply Pressure
NG
min. 1.13 kPa
LPG
min. 2.75 kPa
Manifold Pressure
NG
.94 kPa
LPG
2.55kPa
Electrical: 240 V. 1.13A 60Hz.
Circulation: 2 speed fan, 125/75 CFM.
Log Set: Ceramic fiber, 7 per set.
System Data
FG39 Converted to 31mj.
Burner Inlet Orifice Sizes:
NG
#37 2.65mm
LPG
#52 1.6mm
Max. Input -
NG/LPG
31 Mj/h
Min. Input
- NG/LPG
16 Mj/h
Supply Pressure
NG
min. 1.13 kPa
LPG
min. 2.75 kPa
Manifold Pressure
NG
.89 kPa
LPG
2.55kPa
Electrical: 240 V. 1.13A 60Hz.
Circulation: Variable speed fan, 125/75
CFM.
Log Set: Ceramic fiber, 7 per set.
System Data
FG39 with 40mj.
EV1
EV2
R.Q.
ADJ.
P.OUT
MD
4
3
2
1
Pi
n
11
8
9
10
1
2
3
4
6
7
5
SIT 845 VALVE DESCRIPTION
1)
On-Off Solenoid Valve EV1
2)
On-Off Solenoid Valve EV2
3)
Inlet Pressure Test Point
4)
Outlet Pressure Test Point
5)
Connection for Pressure Regulator /
Combustion Chamber Compensation
6)
Pressure Regulator for Minimum and
Maximum Outlet Pressure
7)
Gas Outlet Pressure Electric Modulator
8)
Pilot Outlet
9)
Main Gas Outlet
10)
Side Outlet
11)
Main Gas Inlet