background image

Regency GF900C-1 Gas Fireplace

17

installation

Description

Simpson

Direct Vent Pro

®

Selkirk

Direct Temp™

American Metal

Products®

Amerivent Direct

Metal-Fab™

Sure Seal

Security

Secure- Vent®

ICC Excel 

Direct

Attic Insulation Shield 12”

46DVA-IS 

N/A@ FPI

N/A

4DAIS12

N/A

SV4RSA

N/A

Attic Insulation Shield - 

Cold Climates

 36”

N/A

N/A

4DAIS12

N/A

N/A

TM-4AS

High Wind Vertical Cap

46DVA-VCH

N/A

N/A

N/A

N/A

TM-4VT

High Wind Horizontal Cap

46DVA-HC

N/A

N/A

N/A

N/A

TM-4DHT

Horizontal Square Termination Cap

See

 

46DVA-HC

4DT-HHC

4DHC

4DHT

SV4CHC-1

TM-4HT

Vertical Termination Cap

46DVA-VC

4DT-HVC

4DVC

4DVT

SV4CGV-1

N/A

Storm Collar

46DVA-08A

4DT-SC

4DSC

4DSC

SV4FC

TM-SC

Restrictor Disk

N/A

N/A

N/A

N/A

N/A

TM-4DS

Extended Vertical Termination Cap

N/A

N/A

N/A

N/A

N/A

N/A

Chimney Conversion Kit  A  (USA only)

46DVA-KCA

N/A

N/A

N/A

N/A

TM-4CA6

Chimney Conversion Kit  B  (USA only)

46DVA-KCB

N/A

N/A

N/A

N/A

TM-4CA7

Chimney Conversion Kit  C  (USA only)

46DVA-KCC

N/A

N/A

N/A

N/A

TM-4CA8

Chimney Conversion Kit Masonry 
(USA only)

46DVA-KMC

N/A

N/A

N/A

N/A

N/A

Wall Firestop

46DVA-WFS

N/A

N/A

N/A

N/A

TM-4TR

Colinear Flex Connectors

46DVA-ADF

N/A

N/A

N/A

N/A

N/A

Adjustable Flashing 0/12-6/12

46DVA-F6

4DT-ST14

4D12S

4DST14

SV4STC14

TF-4FA

Adjustable Flashing 6/12-12/12

46DVA-FLA

4DT-ST36

4D36S

4DST36

SV4STC36

TF-4FB

Vinyl Siding Standoff

46DVA-VSS

4DT-VS

N/A

4DVS

SV4VS

TM-VSS

Vinyl Siding Shield Plate

N/A

4DT-VSP

N/A

N/A

SV4VS

N/A

Snorkel Termination 14”

46DVA-SNKL

N/A

N/A

N/A

N/A

TM-4ST14

Snorkel Termination 36”

N/A

N/A

N/A

N/A

N/A

TM-4ST36

Basic Horizontal Termination Kit (A)

Disc.

4DT-HKA

4DHTK2

4DHTKA

SV-SHK

TM4-HTK

Horizontal Termination Kit (B)

46DVA-KHA

(Changed Components)

4DT-HKB

4DHTK1

4DHTKB

SV-HK

TM4-HTK

Vertical Termination Kit

Disc.

4DT-VKC

4DHTK

4DHTK

SV-FK

N/A

FPI

946-506/P

Vent Guard (Optional) for AstroCap

946-205

Vinyl Siding Shield for Riser Vent Terminal

510-994

Rigid Pipe Adaptor (Must use with all rigid piping)

946-208/P

Vent Guard (Optional) for Riser Vent Terminal

640-530/P

Riser Vent Terminal

946-523/P

AstroCap Horizontal Cap

946-605

Starter Collar Increaser 4” x 6-5/8” to 5” x 8”

946-206

Vinyl Siding Standoff for AstroCap

Note:

   When using Metal-Fab Sure Seal Rigid Piping - please note that the Adaptor (4DDA) must be used in conjunction with FPI Rigid Pipe Adaptor (510-994).

Note:

   Horizontal runs of vent must be level, or have a 1/4” rise for every 1 foot of run towards the termination.  

            Never allow the vent to run downward - this could cause high temperatures and may present a possible fi re hazard.

Offset Pipe Selection:

 Use this table to determine offset pipe lengths.

Pipe Length

(L)

4” x 6-5/8” Venting

For specifi c instructions on venting components - visit the 
manufacturers website listed below.

Run (X)

Rise (Y)

0” (0mm)

4-7/8” (124mm)

13-7/8” (340mm)

Simpson Direct Vent Pro:  www.duravent.com

6” (152mm)

8” (203mm)

16-1/2” (419mm)

Selkirk Direct-Temp: www.selkirkcorp.com

9” (229mm)

10-1/8” (257mm)

18-5/8” (473mm)

American Metal Products: www.americanmetalproducts.com

12” (305mm)

12-1/4” (311mm)

20-3/4” (527mm)

Metal-Fab Sure Seal: www.mtlfab.com

24” (610mm)

20-5/8” (524mm)

29-1/8” (740mm)

Security Secure Vent:  www.securitychimneys.com

36” (914mm)

29” (737mm)

37-1/2” (953mm)

Industrial Chimney Company: www.icc-rsf.com

48” (1219mm)

37-7/16” (951mm)

45-15/16” (1167mm)

Regency Fireplace Products  .  6988 Venture St.  .  Delta, BC  .  Canada  .   V4G 1H4  .  604-946-5155   .  www.regency-fi re.com 

Summary of Contents for GF900C-LPG1

Page 1: ...m a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department 919 500b Greenfire GF900C Gas Fireplace 01 February 2016 Owners Installation Manual www regency fire com au Installer Please complete the details on the back cover and leave this manual with the homeowner Homeowner Please keep these instructions for future reference MODELS GF...

Page 2: ...des helps to differentiate one Remote Control Handset from another so that only the control box with a matching ID code will respond to the appropriate Remote Control Handset To match the control box the following steps are to be followed 1 Ensure the Remote is switched OFF 2 Remove main power to the control box 3 Reconnect main power to the control box 4 Press and hold the PROG and FAN buttons si...

Page 3: ... RESTRICTOR 24 SET TO 0 75mm open 24 Unit Installation with Horizontal Termination 25 4 x 6 5 8 102mm x 175mm flueing 25 Unit Installation with Horizontal Termination 26 Unit installation with Vertical Termination 27 4 x 6 5 8 102mm x 175mm 27 flueing 27 High Elevation 28 Gas Line Installation 28 Pilot Adjustment 28 Gas Pipe Pressure Testing 28 845 S I T Valve Description 28 Aeration Adjustment 28...

Page 4: ...3 Rev A Updated consumption s Dec 23 13 Updated E Aus address Serial Number Regency Gas Fireplace 418 Distributed by To be installed by an authorised person in accordance with installation instructions provided with the appliance Western Australia Air Group Australia 28 Division St Welshpool WA 6106 Eastern Australia Fireplace Products Australia Pty Ltd 1 Conquest Way Hallam VIC 3803 Electrical 24...

Page 5: ...C 1 Gas Fireplace 5 DIMENSIONS dimensions UNIT DIMENSIONS 1192mm 641mm 989mm 438mm Verona Surround Faceplate Dimensions 259mm 76mm 500mm 1091mm 995mm 889mm 332mm 536mm 113mm 14mm 560mm 522mm 160mm 1082mm 795mm 725mm ...

Page 6: ...rical wiring locations in walls and ceilings when cutting holes for termination THIS UNIT MUST ALWAYS TERMINATE FLUE DIRECTLY TO THE OUTDOORS IMPORTANT MESSAGE SAVE THESE INSTRUCTIONS The GF900C Direct Flue Fireplace must be installed in accordance with these instructions Carefully read all the instructions in this manual first Consult the authority having jurisdiction to determinetheneedforapermi...

Page 7: ...al features Refer to the following sections a Crystal Stone Install b Faceplate Door Frame Overlay c Remote Control or Wall Thermostat 9 Final check Before leaving this unit with the customer the installer must ensure that the appliance is firing correctly and operation fully explained to customer INSTALLATION CHECKLIST 1 Locate appliance a Room location Refer to Locating Your Gas fireplace sectio...

Page 8: ...ntel Height min 438mm Top of Fireplace Opening B Sidewall on one side 146mm Side of Fireplace Opening C Ceiling room and or alcove 1003mm Top of Fireplace Opening D Mantel Depth max 305mm 667mm Above Fireplace Opening E Alcove Width 1480mm Sidewall to Sidewall Minimum F Alcove Depth 787mm Front to Back Wall Maximum G From Floor 610mm Top of Fireplace Opening Note 0 No hearth required Installed clo...

Page 9: ...e mantel and the facing is high quality or the paint may discolour MANTEL LEG CLEARANCES Combustible mantel leg clearances as per diagram Allowable mantel leg projection 181mm 254mm 330mm 38mm MANTEL LEG 83mm Non Combustible 102mm 178mm Combustible Material 152mm 305mm 0 Non combustible Facing To Unit Base 667mm 610mm 254mm 660mm Top of Fireplace Opening 508mm 305mm 606mm 438mm Combustible Stud On...

Page 10: ...le The nailing strips can be adjusted back up to 1 1 2 38mm to allow for varying thicknesses in non combustible material wall finishes Nailing Strips INSTALLATION ACCESS PANEL The unit is equipped with a removable access panel for pre finish installation of optional components this panel is located on the lower front face 1 Remove 4 screws to remove access panel 2 Easier access to gas connection w...

Page 11: ...ght 2 5 8 67mm K Gas Connection Inset 1 3 4 44mm L Gas Connection Opening Width 3 1 2 89mm Framing depth measurement is noted with the nailing strips set as far forward on the firebox as possible The nailing strips can be adjusted back up to 1 25mm to allow for varying thicknesses in non combustible material wall finishes NOTE A minimum thickness of 12mm non combustible facing board is required A ...

Page 12: ...iance IMPORTANT Regency Fireplace Products are designed produced tested and certified to the highest industry standards The finishing of the walls surrounding Regency is as critical as the installation itself The temperatures around linear gas fireplaces are typically higher than would be acceptable for the combustible materials Your Regency Fireplace is no exception to this rule Therefore the uni...

Page 13: ...ls See Clearances section Combustible materials can be laid against the side and back standoffs and the stove base 4 Non combustible material ie tile slate etc may be brought up to and overlap the unit top and bottom ensuring that the maximum thickness does not go beyond the 1 1 2 38mm as shown in the diagram below The faceplate will not be able to be mounted if finished material is beyond 1 1 2 3...

Page 14: ... of the flange 1108mm 83mm mm 606 mm 502 1165mm Non combustible Material Non combustible Non combustible Non combustible Header on edge Timber Stud Timber Stud 156mm mm 451 NOTE A minimum thickness of12mmnon combustible facing is required Finished Material Nailing Strip Position 1 2 12mm 1 25mm 1 25mm 1 2 12mm 1 1 2 38mm 0 flush Unit Nailing Strip Flush w unit Factory Set 25mm 12mm Unit Nailing St...

Page 15: ...e window door or non mechanical air inlet or any other opening into a building with the exception of sub floor flueilation see also Note I Appliances up to 150 MJ h input 500 Appliances over 150 MJ h input 1500 k Vertically below an openable window door or non mechanical air inlet or any other opening into a building with the exception of sub floor flueilation I For mechanical air inlets including...

Page 16: ...table Length 7 Black N A N A 4D7AB N A N A N A Extension Pipe 8 1 2 Galvanized 46DVA 08A N A N A N A N A N A Extension Pipe 8 1 2 Black 46DVA 08AB N A N A N A N A N A Adjustable Length 12 Galvanized N A N A 4D12A N A SV4LA12 TC 4dLSI Adjustable Length 12 Black N A N A 4D12A N A SV4LBA12 TC 4dLSIB Extension Pipe 16 Galvanized 46DVA 16A N A N A N A N A N A Extension Pipe 16 Black 46DVA 16AB N A N A ...

Page 17: ...on Kit A Disc 4DT HKA 4DHTK2 4DHTKA SV SHK TM4 HTK Horizontal Termination Kit B 46DVA KHA Changed Components 4DT HKB 4DHTK1 4DHTKB SV HK TM4 HTK Vertical Termination Kit Disc 4DT VKC 4DHTK 4DHTK SV FK N A FPI 946 506 P Vent Guard Optional for AstroCap 946 205 Vinyl Siding Shield for Riser Vent Terminal 510 994 Rigid Pipe Adaptor Must use with all rigid piping 946 208 P Vent Guard Optional for Rise...

Page 18: ...ments diagrams refer to the following instructions 1 Remove the glass door and inner panels see instructions in this manual 2 Remove 6 screws 3 front 3 back to remove heat baffle to access restrictor plate FLUE RESTRICTOR POSITION Set 0 64mm Open Set 2 18mm open Set 1 26mm open Set 3 15mm open Heat Baffle 3 Remove the screws that hold the flue restrictor in place 4 Adjust the flue restrictor plate...

Page 19: ...90o elbow Note Must use optional rigid pipe adapter Part 510 994 when using Rigid Pipe Flueing Systems Maintain clearances to combustibles as listed in Clearances section Horizontal flue must be supported every 0 9m Firestops are required at each floor level and whenever passing through a wall A flue guard should be used whenever the termination is lower than the specified minimum or as per local ...

Page 20: ...LUE 4 X 6 7 8 102MM X 175MM These flueing systems in combination with the GF900 Direct Flue Gas Fireplace has been tested and listed as a direct flue heater system by Warnock Hersey Intertek The location of the termination cap must conform to the requirements in the Flue Terminal Locations diagram in Exterior Flue Termination Locations section Regency Direct Flue Flex System Termination Kits inclu...

Page 21: ...using a Rigid Pipe Adaptor in conjunction with Duraflue Direct Flue Selkirk Direct Temp Ameri Flue Direct Flueing ICC Excel Direct and Security Secure Flue systems Use of these systems with the Rigid Pipe adaptor is deemed acceptable and does not affect the Intertek WHI listing of components WARNING Do not combine flueing components from different flueing systems However use of the the AstroCapTM ...

Page 22: ...tted 2 Minimum distance between elbows is 1 ft 305mm Maintain clearances to combustibles as listed in the Clearances section Horizontal flue must be supported every 3 feet Firestops are required at each floor level and whenever passing through a wall Must use optional rigid pipe adaptor Part 510 994 when using rigid pipe flue systems A flue guard should be used whenever the termination is lower th...

Page 23: ...tems as well as Simpson Dura Flue Direct Flue Ameri can Metal Products Ameri Flue Direct Flue Security Secure Flue ICC Excel Selkirk Direct Temp AstroCapTM is a proprietary trademark of FPI Fireplace Products International Ltd Dura Flue and Direct Flue are registered and or proprietary trademarks of Simpson Dura Flue Co Inc Roof Pitch Minimum Flue Height Feet Meters flat to 7 12 2 0 61 over 7 12 t...

Page 24: ... Maintain clearances to combustibles as listed in the Clearances section Horizontal flue must be supported every 3 feet Firestops are required at each floor level and whenever passing through a wall Must use optional rigid pipe adaptor Part 510 994 when using rigid pipe flue systems Refertothe FlueRestrictorPosition sectionfordetails on how to change the flue restrictor from the factory setting of...

Page 25: ...the adapter over the existing inner and outer flue collar Fasten to the outer collar only with the 3 supplied screws drilling pilot holes will make this easier 4 Level the fireplace and fasten it to the framing using nails or screws through the top and side nailing strips Note For best results and optimum performance with each approved flueing system it is highly recommended to apply Mill Pac seal...

Page 26: ...nation cap faces up there are markings on the cap indicating which way is up This will position the termination cap with proper down slope for draining water Fasten the cap to the outer wall with the 4 supplied screws 6 Pull the centre inner and outer flex liner out enough to slip over the flue collars of the fireplace You may wish to cut the liner shorter to make it more workable Do not bend line...

Page 27: ...fully twist locked position and sealed 5 Cut a hole in the roof centered on the small drilled hole placed in the roof in Step 2 The hole shouldbeofsufficientsizetomeettheminimum requirements for clearance to combustibles of 1 1 2 Slip the flashing under the shingles shingles should overlap half the flashing as per Diagram 3 6 Continue to assemble pipe lengths Note If an offset is necessary in the ...

Page 28: ...ourRegency dealerforfurther instructions Incorrectflamepatternwillhavesmall probably yellow flames not coming into proper contact with the rear burner or flame sensor Burner Flame Sensor Pilot Ignitor PILOT ADJUSTMENT Periodicallycheckthepilotflames Correctflame pattern has two strong blue flames 1 flowing around the flame sensor and 1 flowing across the burner it does not have to be touching the ...

Page 29: ...N 4 5 3 2 1 YELLOW 3 YELLOW BLUE GND BROWN LOW SPEED WHITE RED BLACK FAN 5 3 4 BROWN VIOLET BLUE RED 1 3 2 4 WHITE YELLOW VIOLET BLACK 5 6 1 2 BROWN BLUE VIOLET RED BLACK WHITE YELLOW VIOLET ORANGE ORANGE MODULATING 7 8 6 5 4 3 VALVE RESET SWITCH NC BLACK BLACK 2 1 COIL MODULE SPARK MODULE GROUND MODULE FLAME ORANGE ORANGE 5 4 ORANGE ORANGE GREEN SPARKER RED THERM COMMAND BOX FAN LOW ACTIVE NEUTRA...

Page 30: ...RSION KIT 466 967 FROM NG TO ULPG FOR GF900 USING SIT 845 NOVA GAS VALVE THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS FITTER IF IN DOUBT DO NOT DO THIS CONVERSION 5 Remove rear log tray by removing 3 screws as shown in Diagram 3 below FOLLOWING STEPS FOR GF900C 6 Remove glass crystals and stones if installed 7 Remove 3 screws in locations shown below to remove burner tray Each Kit contains one ...

Page 31: ...ndoing the 3 screws Manoeuvre through antenna 18 Reverse steps 17 16 15 9 for both units For GF900C reverse Steps 8 6 and Step 1 For GF900L reverse steps 5 1 19 Adjust the air shutter opening See page 28 for Aeration Adjust ment 20 Turn on gas supply and plug in power cord Control Box Cover Antenna Jumper Location 17 Remove the jumper using pliers Jumper Diagram 4 Remove Pilot Cap Pilot Cap Pilot ...

Page 32: ...24 Check operation of flame control 25 Check for proper flame appearance and glow on logs C B A Cable Electric Modulator 21 Adjusting the Outlet Pressure All the adjustments must be carried out in the following order Remove the modulator plastic cap A using needle nose pliers Maximum pressure Turn the unit ON to its highest input rating Screw in the nut B to increase the outlet pressure and screw ...

Page 33: ...light that lead to pilot flame Ensure the crystals or stones do not overlap excessively as this will effect the flame pattern 1 Start installing Crystals on the Burner 2 Distribute Crystals evenly starting from back of Firebox Floor 3 Work Crystals from back to front edge of Firebox Floor 4 Ensure Crystals DO NOT block the front of the pilot hood and flame to light the burner VOLCANIC STONES INSTA...

Page 34: ...EMOVAL INSTALLATION 3 Remove two 2 screws in locations shown below to release panel clips 4 Remove 3 screws in locations shown below to remove burner tray 919 615 11 05 15 1 OPTIONAL FINISHING TRIM INSTALLATION tooltip tooltip 1 Install the optional finishing trim by lining up trim with the outside of the fascia Press trim inward firmly to seat onto the unit Note magnets will keep the trim in plac...

Page 35: ...st to the door frame overlay out of the 3 so that the faceplate and door frame overlay are flush with one another See diagram 2 1 Install the fascia to the unit by hooking the left and right side mounting brackets into the mounting slots at the side ofthe firebox as shown below Diagram 3 Diagram 4 Deflector Installed NOTE When installing the stainless steel fascia gloves should be worn to prevent ...

Page 36: ...wn in Diagram 1 3 Install Screen and Inner Door Frame to unit but hanging over glass door frame as shown in Diagram 3 Lower gently once in position over glass door frame 2 Bend Tab on Screen Mesh to 90º as shown in Diagram 2 Secure to Inner Door Frame with one 1 screw as shown in Diagram 2a Diagram 1 Diagram 3 Diagram 2 Diagram 2a ...

Page 37: ...s switched on pressing and releasing this button once will switch the unit off Flame Increase If the unit is switched on pressing and releasing the flame plus button once will increase the flame height to the next available high setting Decrease If the unit is switched on pressing and releasing the flame minus button once will decrease the flame height to the next avail able low setting Fan Increa...

Page 38: ...ier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supplier from a neighbors phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department B Do not use this appliance if any part has been under water Imme...

Page 39: ...ns shown below 8 Loosen three 3 screws to remove heat deflector shown in Diagram 5 9 Remove two 2 screws to remove fan shown in Diagram 6 10 Reverse steps to reinstall fan 7 Remove valve tray by removing fourteen 14 screws in locations shown in Diagram 4 Diagram 5 Valve Tray Screws Diagram 4 Heat Deflector Screws Diagram 6 Fan Screws Diagram 2 Burner Screw Locations Diagram 3 Air Deflector Screw L...

Page 40: ... Check the Flueing System for corrosion in areas that are exposed to the elements These will appear as rust spots or streaks and in extreme cases holes These components should be replaced immediately 2 Remove the Cap and shine a flashlight down the Flue Remove any bird nests or other foreign material 3 Check for evidences of excessive condensation suchaswaterdropletsforming in the inner liner and ...

Page 41: ...approx 1 minute Then turn on again NOTE On initial light up this may occur a number of times until any residual air is purged from the gas line through the burner system It is essential the required waiting time as stated in the manual is observed prior to attempting re ignition After rese翿 ng ignition module unit still not Turn burner switch to ON fans will operate within 5 secs listen for audibl...

Page 42: ... repeat steps 1 5 on the other lower door latch 6 Pull the bottom of the door towards you until the door is angled away from the firebox by about 30 Lift the door up and over the upper door hooks 7 To install the glass door reverse steps 1 Insert the door tool into the lower door latch WARNING Do not operate the appliance with the glass panels removed cracked or broken Replacement of the glass pan...

Page 43: ... ROOM TEMPERATURE ALL POWER IS DISCONNECTED AND GAS SUPPLY IT TURNED OFF 1 Remove faceplate inner frame glass door and inner panels see instructions in this manual 2 Remove crystals and stones if installed 3 Remove burner side panels by lifting out as shown in Diagram 1 4 Remove burner by removing 2 screws in locations shown below Diagram 2 Burner Screw Locations Diagram 3 Air Deflector Screw Loca...

Page 44: ...N A N A 910 089 Flame Cable N A N A N A N A N A N A N A N A 910 088 Spark Cable N A N A N A N A N A N A N A N A 910 084 Control Box N A N A N A 911 101 Control Box N A N A N A N A N A N A 910 527 Manual Control Switch N A N A N A N A N A N A 910 080 Valve 910 521 Control Box Cable 1 910 522 Control Box Cable 2 910 523 Control Box Cable 3 910 525 Control Box Cable 4 N A 2 1 1 3 N A 2 N A N A 910 91...

Page 45: ...ve Assy LP 466 578 P GF 900 Valve Assy NG 19 466 060 Left Panel 20 466 061 Right Panel 21 466 096 Rear Panel 22 466 071 Left Ceramic Filler 23 466 072 Right Ceramic Filler 24 904 966 0 250 20 x 7in Hex Bolt 25 296 122 Door Spring 1 2 x 7 Stainless Steel 26 904 143 HEX NUT 1 4 20 27 476 062 Panel Clip 28 466 083 Heat Exchanger Gasket 29 466 088 Panel Bracket LH 30 466 089 Panel Bracket RH 31 466 54...

Page 46: ...46 Regency GF900C 1 Gas Fireplace PARTS LIST parts list 5 5 9 32 33 29 19 21 27 31 35 16 13 30 20 34 MAIN ASSEMBLY ...

Page 47: ...ption 32 467 922 Inner door frame Black w Screen 467 932 Inner door frame Stainless w Screen 33 467 544 Door Frame Overlay Black 34 467 938 Fascia and Door Frame Black w Screen 467 936 Fascia and Door Frame Stainless Steel w Screen 35 467 951 Fascia Black Glass not shown 32 33 34 ...

Page 48: ...48 Regency GF900C 1 Gas Fireplace NOTES notes ...

Page 49: ...Regency GF900C 1 Gas Fireplace 49 NOTES notes ...

Page 50: ...l installations must be performed by a qualified gas fitter and installed according to all applicable local and national codes Also all service work must be carried out by a qualified gas service person provided by the selling dealer It is the responsibility of the installer to ensure that the appliance is firing as per rating plate Any part or parts of this unit which in our judgement show eviden...

Page 51: ...er Holdings 28 30 Division St 1 3 Conquest Way 17 Mainstreet Place Welshpool WA 6106 Hallam VIC 3803 Te Rapa Ha 3200 08 9350 2200 03 9799 7277 07 849 7585 NOTE PLEASE RETAIN YOUR INVOICE AS PROOF OF PURCHASE FOR WARRANTY VERIFICATION INCORRECT INSTALLATION OR GAS PRESSURE SETTINGS ARE NOT COVERED BY WARRANTY A SERVICE OR CALLOUT FEE WILL BE CHARGED IN THESE CIRCUMSTANCES ...

Page 52: ...___________________________ Date Installed _______________________________________________________ Serial No ___________________________________________________________ Register your Regency warranty online www regency fire com au Reasons to register your product online today View and modify a list of all your registered products Request automatic email notification of new product updates Stay inf...

Reviews: