20
Regency Horizon™ HZ42STE Gas Fireplace
INSTALLATION
Notes:
1) Liner sections should be continuous without any
joints or seams.
2) Only Flex pipe purchased from Regency
®
may be
used for Flex installations
3) Horizontal vent must be supported every 3 feet.
4) Regency
®
Direct Vent System (Flex) is only approved
for horizontal terminations.
5) Flex system can only be used up to a maximum
continuous vent length of up to 10 feet. If longer
runs are required, rigid pipe must be used.
FPI Kit #
Length
Contains:
#946-513
2 Feet
1)
6-5/8”
fl exible outer liner (Kit length)
2)
4”
fl exible inner liner (Kit length)
3)
spring
spacers
4)
thimble
5)
AstroCap
termination cap
6)
screws
7)
tube of Mill Pac
8)
plated
screws
9)
S.S. screws #8 x 1-1/2” drill point
#946-515
4 Feet
#946-516
10 Feet
HORIZONTAL TERMINATIONS
FLEX VENT 4" X 6-5/8
"
These venting systems, in combination with the HZ42STE Direct Vent Gas Fireplace, has been tested and listed as a direct vent heater system by
Warnock Hersey/ Intertek. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in "Exterior
Vent Termination Locations" section.
Regency
®
Direct Vent (Flex) System Termination Kits includes all the parts needed to install the HZ42 using a fl exible vent.