Figure 1: Power Vent Kit’s Parts Diagram.
Please ensure that your Power Vent Kit has not been
damaged.
1. Plan out the venting and wiring installation. Important
notes to consider when planning where the venting will be
installed:
•
Minimum horizontal vent run allowed with no rise
is 1 foot (305mm).
• Horizontal vent runs less than 8 feet (2.44m) require
a 60% restrictor. Refer to the Owner’s Manual on how to
install a restrictor.
• Maximum vent run is 100 feet (30.5m) (H
1
+ V + H
2
+
H
3
+ H
4
+ H
5
+ H
6
), refer to Figure 2.
• Maximum below-grade installation is 8 feet (2.4m) (V).
• Multi-elbow installations are possible up to a maximum
of six 90°.
• See Figure 4a for the typical overall dimensions with a
minimum horizontal vent installed.
• Refer to Figure 19 and Table 1 for vent termination
clearances and restrictions.
• Approved vent systems are as follow when using 4” x
6-5/8” pipe.
Simpson duravent, Security Chimney, American Metal,
Selkirk Int. Metal Fab., Excel Direct.
Item
Description
1
5”x8” to 4”x6⅝” Vent Reducer*
2
4”x6⅝” Wall Thimble
3
Power Vent Assembly
4
Power Vent Control Box
* Item not included
H1
V
H2
H3
H4
H5
H6
5"x8"
90
o
Elbow
5"x8" to 4"x6
5
/
8
"
Vent Reducer
4"x6
5
/
8
"
90
o
Elbow
Power Vent
Figure 2: Below-grade installation with maximum number of elbows.
POWER VENT KIT INSTALLATION:
30
| HZ965/L965 Gas Fireplace
|
30
installation
Summary of Contents for Horizon HZ965E
Page 52: ...SAFETY SCREEN INSTALLATION 52 HZ965 L965 Gas Fireplace 52 installation ...
Page 66: ...66 HZ965 L965 Gas Fireplace 66 parts list ...
Page 72: ......
Page 73: ...HZ965 L965 Gas Fireplace 73 73 notes ...
Page 74: ...74 HZ965 L965 Gas Fireplace 74 notes ...
Page 75: ......