U37-1 Regency
®
ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove
9
INSTALLATION
COMBUSTION AND
VENTILATION AIR
The combustion air from this appliance is drawn
from outside the building through the outer fl ue.
Extra provision for combustion air inside the
room is not required.
VENTING
The Regency
®
Direct Vent System (Horizontal
Termination Kit (640-944) and the Vertical
Termination with the Co-linear Flex System in
combination with the ULTIMATE Direct Vent-
Rear Freestanding Gas Stoves (U37-NG1 and
U37-LP1) have been tested and listed as direct
vent heater systems by Warnock Hersey.
The Horiz. Termination Kit (640-944) includes
everything required for a straight through the
wall installation, or add a 45
o
elbow for a corner
installation. If a snorkel termination is required,
the Simpson Dura-Vent Direct Vent System
Model DVGS terminals are available.
INSTALLATION
CHECKLIST
1)
Locate your appliance. Refer to the following
sections:
a. Clearances to Combustibles
b. Locating your Ultimate Gas Stove
c. "Venting" to "Rigid Pipe Venting -
Vertical Terminations" sections.
2)
Install venting. See "Planning Your Venting
Installation" to "Vertical Termination with
Co-Linear Flex System" sections.
3)
Make gas connections. Refer to the "Gas
Connection" section.
Test the pilot. Must be as per diagram in the
"Maintenance Instructions" section.
4)
If necessary, convert from Natural Gas to
Propane. Refer to the "Conversion Kit from
NG to LPG" section.
5)
Installl standard and optional features. Refer
to the following sections where applicable:
a. Log Set Installation
b. Door Installation
c. Louver Installation
d.
Wall
Thermostat
e. Remote Control
6)
Final check. Refer to the "Final Check" sec-
tion.
Before leaving this unit with the customer, the
installer must ensure that the appliance is fi r-
ing correctly and
operation fully explained
to customer.
This includes:
1)
Clocking the appliance to ensure the correct
fi ring rate (rate noted on label) after burning
appliance for 15 minutes.
2)
If required, adjusting the primary air to ensure
that the fl ame does not carbon. First allow
the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that
causes sooting or carboning that results
in damage is not the responsibility of the
manufacturer.
MANUFACTURED
MOBILE HOME
ADDITIONAL
REQUIREMENTS
1)
Ensure that structural members are not cut
or weakened during installation.
2)
Ensure proper grounding using the #8 ground
lug provided.
3)
Appliance must be anchored to the fl oor with
the supplied anchoring methods.
CLEARANCES TO
COMBUSTIBLES
The clearances listed are MINIMUM distances.
Measure the clearance to both the appliance and
the chimney connector.
The farthest distance is
correct if the two clearances do not coincide.
For example, if the appliance is set as indicated
in one of the diagrams but the connector is too
close, move the stove until the correct clearance
to the connector is obtained.
This appliance may be installed only with the
clearances as shown in the situations pictured.
Do not combine clearances from one type of
installation with another in order to achieve
closer clearances.
This unit can be installed on a solid combustible
surface like a wood fl oor. This unit can also be
installed directly on carpeting or vinyl when the
bottom pedestal cover plate (provided with unit)
is installed.
Use the minimum clearances shown in the dia-
grams below:
Clearances
A Side Wall to Unit
7-1/2" / 190 mm
B Back Wall to Unit
3" / 76 mm
E Side Wall to Unit
4-1/2" / 114 mm
Reference Dimensions
C Floor to Flue Centerline
25" / 635 mm
D SideWall to Flue Centerline20-1/2" / 521 mm
LOCATING YOUR
GAS STOVE
When selecting a location for your stove, ensure
that the clearances listed above are met as well
as ensuring that there is adequate accessibility
for servicing and proper operation.
For Vent Termination requirements, see the
"Exterior Vent Terminal Locations" section.
This appliance is Listed for bedroom installations
when used with a Listed Millivolt Thermostat.
Some areas may have further requirements,
check local codes before installation.
This appliance is Listed for Alcove installations,
maintain minimum Alcove clearances as follows,
minimum ceiling height of 66"(1.7m), minimum
width of 41"(1.0m) and a maximum depth of
36"(0.9m).
Minimum ceiling height
is 36" / 914 mm from
top of unit.
A) Cross
Corner
B)
Flush with Wall/Alcove
C) Flat on Wall Corner
D) Flat on Wall