Vertical Discharge Condensate Installation
Note
The Kinetic Advance condensate outlet is compatible with standard 22 mm plastic push-fit fittings and
32mm plastic waste pipe fittings.
A water trap with a seal depth of at least 60mm or a HepVo valve must be fitted between the unit and the
rest of the waste system.
Wastepipes must have a 3 degree minimum angle to allow the water to drain away from the unit naturally.
In areas where freezing weather conditions occur, outlet pipes must be insulated to avoid blockage by ice,
which may cause damage to the unit and surroundings.
This installation guide is for a Right Hand configured unit as specified on page 5. If the unit is configured as
Left Hand, then the condensate drain should be installed on the left with the blanking cap on the right.
22mm waste pipe
Step 1:
Solvent weld a small piece of
22mm plastic waste pipe to the (RH)
condensate outlet.
Step 2:
Attach the appropriate pipe
fittings for your installation. Always use a
demountable coupler close to the unit.
Fit the drain cap supplied with the unit to
the opposite (LH) condensate outlet.
Ensure the sealing gasket is fitted inside
the blanking cap.