26
Sentinel Kinetic Advance S, SX - www.regulus.eu
Unit configuration
Select the orientation of the unit depending on the
configuration of the installation. Units with a preheater
are preconfigured from the factory and cannot be
changed.
See page 11 for a description of the unit handling.
Press
to save and return to the commissioning menu.
Filter Check
Select the time interval for checking the filters using the
/
-
buttons on the screen, between 1 month and
18 months.
Note: There is an automatic filter check notification
3 months after installation, irrespective of set intervals.
Service interval
Set the service frequency.
Reset Service Timer
After the unit has been serviced, use this option to reset
the timer.