Diagnosing a Problem
In the event of a problem, always troubleshoot the unit according to:
Fault code
displayed on the Control Unit.
Fault LED
if connected.
If no indications are displayed, then troubleshoot problem according to the fault symptom as described in
the following tables.
Service/Fault Code Screens alternating
The Fault Code notification is displayed, when a
fault has occurred. Take note of the fault code
when reporting a fault.
For assistance contact the service provider and quote the fault code number and the product serial number
which can be found behind the front cover.
Note that the fault code is not displayed until the fault has been present for 3 minutes.
The following fault codes numbers may be displayed.
Code numbers are added together if more than one fault is detected.
For example: Code 03 indicates that both left and right fans are not running.
Code
Problem
01
Left Fan Fault
02
Right fan Fault
04
Left Thermistor Fault
08
Right Thermistor Fault
16
Left Centre Thermistor Fault
32
Right Centre Thermistor Fault
64
Left Centre Temp/Humidity Sensor Fault
128
Right Centre Temp/Humidity Sensor Fault
Table 3: Fault Codes