19
OPERATING AND MAINTENANCE MANUAL
Chapter 7 - Electronic Board
TAE K15÷K20
The data in this manual are not binding and may be changed by the manufacturer without notice.
Reproduction of this manual, even partial, is strictly prohibited.
7 . 1 2 F u n c t i o n m e n u (
!
b u t t o n )
The access to Function Menu allows to:
1.
Display and reset the alarms (see 7.12.3 “
How to display the alarms “ALrM””
).
Reset the alarms (see “
How to reset an alarm “rSt””
).
2.
Display the alarm history (see 7.12.5 “
How to display the alarm historic “ALoG””
).
3.
Upload the parameters from the unit to the key.
4.
Display the operating hours of the controlled loads.
Reset the operating hours of the controlled loads.
7.12.1 Access to Functio n men u
Press and release
!
button (menu).
The icon “
0
” will appear.
7.12.2 Exit Fu nct ion menu
Press and release
!
button or wait for time out (30 seconds).
The icon “
0
” disappears.
7.12.3 How to display t he alarms “AL rM”
1.
Press
!
to enter Function menu.
2.
Press
>
or
"
to select “
ALrM
” function.
3.
Press and release
4
button.
4.
Press
>
or
"
to scroll all alarms.
5.
To exit press
!
or wait for time out (30 seconds).
7.12.4 How to reset an alarm “rSt”
1.
Press
!
to enter Function menu.
2.
Select “
ALrM
” function
3.
Press
4
, in the bottom of the display it appears the alarm code.
4.
If the alarm can be reset in the top of the display it appears the Label “
rSt
”, it the alarm can not be reset it appears the Label “
NO
”.
5.
Use
>
or
"
button to scroll all the alarms.
6.
When the Label “
rSt
” is displayed, press
4
to reset the alarm and go to the following one.
7.
To exit press
!
button or wait for time out (30 seconds).
7.12.5 How to display t he alarm h istoric “ALoG”
1.
Press
!
button to enter Function menu.
2.
Use
>
or
"
button to select the function “
ALoG
”.
3.
Press
4
until the Label with the alarm code will appear in the bottom of the display, and the Label “
n°
” with a progressive number
will appear in the top of the display.
4.
Using
>
or
"
button scroll all the alarms.
5.
To exit “
ALoG
” function and to return to normal displaying, press
!
button or wait for time out (30 seconds).
The memory contains until 50 alarms, a further alarm will cancel from the memory the oldest one (the displaying is in increasing order, from the
oldest one to the most recent one).
7.12.6 How to reset the alarm history “ArSt”
1.
Enter Function menu.
2.
Select “
ALoG
” function in the bottom of the display.
3.
Press
4
button.
4.
Inside “
ALoG
” function, using
>
or
"
button, select the function “
ArSt
” in the bottom of the display and “
PAS
” in the top of
the display.
5.
Press
4
: the password is required. In the bottom of the display it appears “
PAS
”, “
0
” flashes in the top of the display.
6.
Insert the password for resetting.
7.
If the password is correct the Label “
ArSt
” flashes for 5 seconds to confirm the resetting.
After resetting the unit returns to normal displaying.