Sequence to undo the fixed contact from the ferrule in PA66.
In case of removable fixed contacts. it is perfectly normal to have a slight joint tolerance
between fixed deck, nylon ferrule and contact
–
it does not compromise the tap changer
functioning.
C.A.P.T. highly recommends using flexible cables to execute connections on the tap
changer. Furthermore, the cables must not weight in any way on the tap changer.
6.
DRYING PROCEDURE
6.1
Drying procedure
Different drying treatment can be processed by customer: oven, in a vacuum autoclave, vapor-
phase or other. In this process the tap changer is normally included too. The maximum
temperature suggested by C.A.P.T. for our tap changers is 100°C-120°C for 24-36 hours.