3.2
Storage
The DETC must be stored in its packaging, in dry place with temperature in the range of
-10 °C / +40 °C.
Upon receive the DETC, please check:
•
The outer surface of the packaging must be intact.
•
That there are no breakages.
In case you detect any damages, please contact C.A.P.T. office informing the DETC serial number.
4.
USE AND MAINTENANCE
4.1
Use
This is a de-energized tap changer. It means all switching operations must be
performed after disconnecting transformer by the electrical net opening the
sectionalizing switches, both HV and LV side, so transformer becomes off-circuit
Do not operate while the transformer is energized. Such operation may result in
failure of the transformer and injury or death to the operator.
•
To operate the tap-changer open the sectionalizing switches, both HV and LV side, so
transformer becomes de energized
•
If installed, remove the padlock (figure 1, 2)
•
Lift axially the knob (figure 3), turn the knob (figure 4) and insert it in the new position
(figure 5). The action of a spring facilitates this last operation.
•
Install the padlock (figure 6).