Calculation of storage capacity 

The size of the data memory is 512Kbyte. Versions with 1 MByte, 2MByte or 4Mbyte 
are under prparation. Worst case the M-Bus frame can be 261 bytes long, but mostly 
the telegrams are much shorter. A typical heat meter for example transmits 79 bytes. 
Water meters and pulse adaptors often use even shorter frames. A length field and a 
point of time is additionally stored with the M-Bus frame. This adds 12 Bytes. In our 
example 60 heat meters with 79 bytes M-Bus frame + 12 bytes occupy  5462 bytes 
inside the FLASH for every readout. The FLASH is organized as a ring memory with 8 
blocks of 64kB (65536 bytes) or in total 512kB. If the current block is full, the next block 
will be erased completely. So it could happen that only 7 block are full with data. In this 
example there is enough memory to store minimum 7 x 65536 / 5462 = 83 readouts.The 
practice shows that usualy there are often installations with less meters and shorter M-
Bus telegrams. 
 

Download of stored data 

The contents of the data memory can be downloaded in command mode using a direct 
or a modem connection with FService or Dokom CS.  
 
The most current readouts are also available via keyboard and LCD. The menu “Data 
exchange” shows a list with the last 25 readout times. You can scroll through the 
different points of time and select one with the E button. Then the data of all meters for 
this readout is displayed in the same manner as with “Readout of all”. 

 

7 PC-Software FService 

 
The devices can be operated via keyboard without software or as simple level 
converters with any M-Bus software. The software FService offers a comfortable access  
to and control of the Datalogger and M-Bus Display. The software can work locally with 
a PC or remotely via a modem. 
 
The software is described in a special document delivered with Fservice. 

Summary of Contents for MR004C

Page 1: ...es Article no MR004C Level converter for 60 unit loads in housing for DIN rail MR04W Level converter for 60 unit loads in wall mountable housing MR004FA Remote display and level converter for 60 unit...

Page 2: ...Datalogger MR004DL Both devices can be operated as a transparent level converter and as a remote display with keyboard or by remote control The datalogger adds the possibility to automatically read a...

Page 3: ...ceive of PC RS485 S S Terminals for RS 485 interface observe polarity M Bus M M M Bus terminals 3 pairs M Bus devices are wired polarity independent in parallel to the same line The signs mark only th...

Page 4: ...s active Handshake unused Pin 1 6 and 9 are not connected RS485 interface The PW60 normally activates the receive mode on the RS485 On reception of data from the M Bus slaves it switches to transmit m...

Page 5: ...he number of connected meters You can connect 60 meters specified with 1 unit load 1 5mA but only 30 meters specified with 2 unit loads 3mA Are there defective slaves or open cable ends lying in the e...

Page 6: ...loads with power Technical data Supply Voltage 230VAC 50Hz 25W respective 110VAC 50Hz 25W US version Environment Operating temperature 0 45 C Storage temperature 10 60 C Humidity 10 70 non condensing...

Page 7: ...he cable diameter The maximum allowed resistance of the cable RL between the MR004DL FA can be estimated with the following formulas N no of unit load each 1 5mA N slaves at end of cable RL 9467 15 x...

Page 8: ...ith LEDs under the terminal lid compartment and also on the LCD If there are problems with interpretation of the M Bus data the display shows Status Error The list of errors is shown on the LCD after...

Page 9: ...ng Fservice the device includes 4 keys and a backlighted display for comfortable local access to all functions The buttons give a very precise mechanical feedback and each input is acknowledged by an...

Page 10: ...activated temporary or permanent error bist in the Status byte an E will be shown The first character follows one digit for the device 0 main device Filtering data To make the readout of data easy th...

Page 11: ...ed to these functions Shows the list of slaves Allows editing of Primary address ID and baudrate The meter data of all devices are read and displayed on the LCD based on the list of slaves After selec...

Page 12: ...YY Shows the ID of location description Change of passcode B global access Selects passcode mode Standard requests passcode on startup Access by ID Adr requests ID address for single read Manually sta...

Page 13: ...tected meters You should check the entries of the list of slaves from the menu List of slaves Show edit list Editing the list of slaves The entries in the list of slaves can also be edited by the user...

Page 14: ...upport this format Therefore we offer a special solution called M Bus modem for use with any level converter and also with MR004DL FA in level converter mode In spite of this the command mode makes us...

Page 15: ...ll with data In this example there is enough memory to store minimum 7 x 65536 5462 83 readouts The practice shows that usualy there are often installations with less meters and shorter M Bus telegram...

Page 16: ...rminal and connect the PC to the modem Choose 9600 baud 8 data bits no parity and one stopbit Then input the following commands each activated by the Enter key Command Function AT for baudrate detecti...

Reviews: