07.03.02, Version 1.2 

User manual MR004DL/FA 

 

GmbH, Stettiner Str. 38, D-33106 Paderborn

2 Description of the M-Bus Level Converter 

 

Functionality: 

The RS232C and RS485 interface signals are directly connected to the M-Bus all the 
time besides during the operation via keyboard, the remote access using the command 
menu and the automatic readout. External connected controllers (laptop, building 
control systems ..) can use the device during the inactivity as a level converter for the 
physical layer of the M-Bus. The software of the controller must provide the 
communication protocols of the connected meters. The members of the W60 family are 
able to supply up to 60 slaves (unit loads) with power. 
 
 

Technical data 

Supply:  Voltage:   230VAC, 50Hz, 25W  respective 
       110VAC, 50Hz, 25W (-US version) 

Environment:  Operating temperature:    0..+45°C  

Storage temperature: -10..+60°C 

   Humidity:   10..70% (non condensing) 

Housing:  Dimensions:   W x H x L = 166 x 190 x 112 (mm) 
   Protective class:  IP53 (cable glands must be closed) 
   Material / colour:  PS / light-grey (similar to RAL 7035) 

Weight:  1,3kg 

 

M-Bus specifications 

 

Parameter 

min. 

typ. 

max. 

unit 

Max. no. of unit loads (slaves) 

60 

 

 

 

Internal resistance 

 

 

15 

 

Bus voltage mark = log. 1 (@ 0mA) 

38,5 

39,0 

39,5 

Voltage drop for space = log. 0 

12 

12,5 

13 

Warning current level (Max LED) 

90 

100 

110 

mA 

Level for over current interruption (Short LED) 

130 

140 

160 

mA 

Level for bit detection from slave 

 

 

mA 

Level for collision detect 

 

30 

 

mA 

 
1 unit  load = 1.5mA

 

 
The device transmits a break signal (space) for minimum 50ms after a collision and for 
minimum 100ms after a short circuit. 

Summary of Contents for MR004C

Page 1: ...es Article no MR004C Level converter for 60 unit loads in housing for DIN rail MR04W Level converter for 60 unit loads in wall mountable housing MR004FA Remote display and level converter for 60 unit...

Page 2: ...Datalogger MR004DL Both devices can be operated as a transparent level converter and as a remote display with keyboard or by remote control The datalogger adds the possibility to automatically read a...

Page 3: ...ceive of PC RS485 S S Terminals for RS 485 interface observe polarity M Bus M M M Bus terminals 3 pairs M Bus devices are wired polarity independent in parallel to the same line The signs mark only th...

Page 4: ...s active Handshake unused Pin 1 6 and 9 are not connected RS485 interface The PW60 normally activates the receive mode on the RS485 On reception of data from the M Bus slaves it switches to transmit m...

Page 5: ...he number of connected meters You can connect 60 meters specified with 1 unit load 1 5mA but only 30 meters specified with 2 unit loads 3mA Are there defective slaves or open cable ends lying in the e...

Page 6: ...loads with power Technical data Supply Voltage 230VAC 50Hz 25W respective 110VAC 50Hz 25W US version Environment Operating temperature 0 45 C Storage temperature 10 60 C Humidity 10 70 non condensing...

Page 7: ...he cable diameter The maximum allowed resistance of the cable RL between the MR004DL FA can be estimated with the following formulas N no of unit load each 1 5mA N slaves at end of cable RL 9467 15 x...

Page 8: ...ith LEDs under the terminal lid compartment and also on the LCD If there are problems with interpretation of the M Bus data the display shows Status Error The list of errors is shown on the LCD after...

Page 9: ...ng Fservice the device includes 4 keys and a backlighted display for comfortable local access to all functions The buttons give a very precise mechanical feedback and each input is acknowledged by an...

Page 10: ...activated temporary or permanent error bist in the Status byte an E will be shown The first character follows one digit for the device 0 main device Filtering data To make the readout of data easy th...

Page 11: ...ed to these functions Shows the list of slaves Allows editing of Primary address ID and baudrate The meter data of all devices are read and displayed on the LCD based on the list of slaves After selec...

Page 12: ...YY Shows the ID of location description Change of passcode B global access Selects passcode mode Standard requests passcode on startup Access by ID Adr requests ID address for single read Manually sta...

Page 13: ...tected meters You should check the entries of the list of slaves from the menu List of slaves Show edit list Editing the list of slaves The entries in the list of slaves can also be edited by the user...

Page 14: ...upport this format Therefore we offer a special solution called M Bus modem for use with any level converter and also with MR004DL FA in level converter mode In spite of this the command mode makes us...

Page 15: ...ll with data In this example there is enough memory to store minimum 7 x 65536 5462 83 readouts The practice shows that usualy there are often installations with less meters and shorter M Bus telegram...

Page 16: ...rminal and connect the PC to the modem Choose 9600 baud 8 data bits no parity and one stopbit Then input the following commands each activated by the Enter key Command Function AT for baudrate detecti...

Reviews: