F1-28 Series Sprinklers Summary

Sprinkler 

Model

K-Factor gpm/psi

1/2

 

(lpm/bar

1/2

)

Orientation

Listings & Approvals

Max. Working Pressure 

psi (bar)

Sprinkler 

Identification 

Number (SIN)

F1-28

2.8 (40)

Upright

cULus

175 (12)

RA1321

Pendent

175 (12)

RA1311

Table A

Model F1-28 Pendent

Model F1-28 Upright

Features

• 

Standard coverage standard-response sprinklers

• 

Upright and pendent deflectors

• 

Low profile, compact design

• 

Available in a wide variety of finishes

Product Description

Reliable Model F1 series sprinklers are standard-response 

standard spray automatic fire sprinklers utilizing a 5.0 mm glass 
bulb thermal element.

Pendent and horizontal sidewall sprinklers may be installed 
exposed or surface mounted using escutcheons such as the 
Reliable Models B, C, or HB (reference Technical Bulletin 204). 
When installed recessed, the Model F1-28 series sprinklers 
are specifically listed with and may only be installed with listed 
Reliable escutcheons. Refer to the technical information on the 
following pages for specific listings for recessed installations and 
refer to Figure 3 for dimensional information.

When fitted with an approved water shield, these sprinklers may 
considered intermediate sprinklers for use in racks, below grated 
walkways, and other areas where intermediate level sprinklers are 

required.

Table A provides a summary of the approvals and availability of 
specific Model F1-28 series sprinkler configurations. Additional 
technical information for each sprinkler model is provided on the 

following pages.

Note:

 This bulletin may contain information on New and Legacy 

sprinklers that reflects a dimensional change only. Sprinkler
Identification Number (SIN), application, performance, an listings/
approval are not otherwise affected. Sprinklers with new frames 
can be identified by a rotoclip indent on one side of the wrench 
boss and in some cases an installed rotoclip. Sprinklers with new 
frames will include the suffix “N” in the order. For reference only, 
legacy version of this sprinkler can be found on Technical Bulletin 

013.

www.reliablesprinkler.com

K-factor 2.8 (40) 

F1-28 Series 

Standard-Response Sprinklers

Bulletin 066 May 2021

Summary of Contents for F1-28 Series

Page 1: ...tion on the following pages for specific listings for recessed installations and refer to Figure 3 for dimensional information When fitted with an approved water shield these sprinklers may considered intermediate sprinklers for use in racks below grated walkways and other areas where intermediate level sprinklers are required Table A provides a summary of the approvals and availability of specifi...

Page 2: ...ector Brass Alloy Sprinkler Finishes See Table B Sensitivity Standard Response Temperature Ratings 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C 286 F 141 C 360 F 182 C 500 F 260 C Guards Shields New Frames F 1 Guard Kit F 3 Guard Shield Kit Guards Shields Legacy Frames D 1 Guard Sprinkler Wrench Model W2 Model J New frame with guard installed Model JD Legacy frame with guard installed Listings and ...

Page 3: ... 79 C 200 F 93 C 286 F 141 C 360 F 182 C 500 F 260 C Recessed Escutcheons Model F1 Model F2 Model FP Guards Shields New Frames 2 F 7 Guard F 8 Guard Shield Kit Guards Shields Legacy Frames 2 D 1 Guard Sprinkler Wrenches Model W2 pendent Model W4 recessed Model J New frame with guard installed Model JD Legacy frame with guard installed Listings and Approvals cULus Notes 1 286 F 141 C and higher tem...

Page 4: ...Recessed Installation Pendent Sprinklers Figure 3 FP Escutcheon F1 Escutcheon F2 similar Bulletin 066 May 2021 Page 4 of 6 www reliablesprinkler com ...

Page 5: ...ated Black Paint Black Paint Off White Off White Chrome Dull Chrome Dull Notes 1 Other finishes and colors are available on special order Consult your Reliable sales representative for details 2 Paint or any other coating applied over the factory finish will void all approvals and warranties 3 The Model FP assembly consists of a sprinkler mounted in a galvanized steel cup with a finished trim ring...

Page 6: ...ion Upright Pendent Pendent FP Temperature Rating See sprinkler technical specifications Sprinkler Finish See Table B Recessed Escutcheon F1 F2 FP Escutcheon Finish See Table B Sprinkler Wrench Model W2 upright and pendent Model W4 recessed Model J New frame with guard installed Model JD Legacy frame with guard installed Note 286 F 141 C and higher temperature rated sprinklers are not listed to be...

Reviews: