Application

Model F1 Res LL sprinklers are cULus Listed in accor-

dance with UL 1626 for installation in accordance with 
NFPA 13, NFPA 13R, and NFPA 13D. Sprinkler systems 
using Model F1 Res LL sprinklers must be hydraulically 
designed to provide at least the flow identified in the Tech-
nical Data tables in this bulletin. For NFPA 13 installations, 
the flow per sprinkler must be the greater of: (1) the flow 
listed in the applicable Technical Data table and (2) the 
flow required to achieve a minimum design density of 0.1 
gpm/sq ft over the design area of the sprinkler. For cover-
age area dimensions less than those listed in the Technical 
Data tables, use the minimum required flow for the next 
larger max. coverage area listed.

Installation

Models F1 Res LL sprinklers are to be installed as shown.  

Model F1, F2 and FP Escutcheons, illustrated herewith, are 
the only recessed escutcheons to be used with Model F1 
Res LL sprinklers.  Use of any other recessed escutcheon 
will void all approvals and warranties.  For installing Model 
F1 Res LL Pendent sprinklers use only the Model W2 sprin-
kler Wrench; for installing Models F1 Res LL Recessed 

Pendent, CCP & SWC sprinklers use only the Model GFR2 
sprinkler wrench; for installing Model F1 LL Res Recessed 
HSW sprinklers use only the Model GFR2 Sprinkler Wrench. 
Use of wrenches other than those specified may damage 
these sprinklers. Install F1 Res 44 LL with a ceiling to de-
flector distance of 4” - 12”. Flow arrow on deflector must 
point away from near wall and “Top” marking must face 
ceiling. 

Escutcheon*, F1 or F2, Data:

Type

Adjustment

Inch (mm)

“A”

Inch (mm)

Face of fitting 

to ceiling

Inch (mm)

F1

3/4 (19.0)

Min.=

3

/

4

”   (19.1)

Max.=1

1

/

2

” (38.1)

3

/

16

 - 

15

/

16

(4.7 - 24.0)

F2

1/2 (12.7)

Min.=

15

/

16

” (23.8)

Max.=1

1

/

2

” (38.1)

3

/

16

 - 

11

/

16

(4.7 - 17.4)

* Note:

 Escutcheons F1 or F2 may be used with

            Model F1 Res 49 LL & 58 LL Recessed Pendent Sprinkler

• 

Model F1 Res 30 LL, 49 LL & 58 LL Pendent

• 

Model F1 Res 30 LL Recessed Pendent / F2

• 

Model F1 Res 49 LL & 58 LL Recessed Pendent / F1

Fig. 1

Fig. 2

F1 escutcheon, 

3

/

4

” (19mm) adjustment

Summary of Contents for F1 Res 30 LL

Page 1: ...L Recessed Pendent FP F1Res49LL 58LLRecessed Pendent F1 F1 Res 30 LL Recessed Pendent F2 F1 Res 44 LL 58 LL Recessed HSW F2 F1 Res 30 LL 49 LL 58 LL CCP Pendent F1 Res 44 LL SWC Product Description Model F1 Res LL Pendent sprinklers Figs 1 2 3 4 are fast response sprinklers combining excellent durability high sensitivity glass bulb and low profile decorative design The F1 Res LL Horizontal Sidewal...

Page 2: ...el F1 Res LL sprinklers Use of any other recessed escutcheon will void all approvals and warranties For installing Model F1 Res LL Pendent sprinklers use only the Model W2 sprin kler Wrench for installing Models F1 Res LL Recessed Pendent CCP SWC sprinklers use only the Model GFR2 sprinkler wrench for installing Model F1 LL Res Recessed HSW sprinklers use only the Model GFR2 Sprinkler Wrench Use o...

Page 3: ... 79 100 150 38 66 4 9 70 6 2 25 57 Max Coverage area Ft x Ft m x m Max Spacing Ft m Ordinary Temp Rating 155 F 68 C Intermediate Temp Rating 175 F 79 C Top of Deflector to Ceiling Inch mm Minimum Spacing Ft m Flow GPM L min Pressure PSI bar Flow GPM L min Pressure PSI bar 12 x 12 3 6 x 3 6 12 3 6 13 49 7 0 0 48 13 49 7 0 0 48 Smooth Ceilings 1 to 4 25mm to 100mm Beamed Ceilings per NFPA 13 13D or ...

Page 4: ...2 25 57 Max Coverage area Ft x Ft m x m Max Spacing Ft m Ordinary Temp Rating 155 F 68 C Intermediate Temp Rating 175 F 79 C Top of Deflector to Ceiling Inch mm Minimum Spacing Ft m Flow GPM L min Pressure PSI bar Flow GPM L min Pressure PSI bar 12 x 12 3 6 x 3 6 12 3 6 16 61 7 6 0 53 16 61 7 6 0 53 Smooth Ceilings 1 to 4 25mm to 100mm Beamed Ceilings per NFPA 13 13D or 13R 8 2 4 14 x 14 4 3 x 4 3...

Page 5: ... Ft m Flow GPM L min Pressure PSI bar 12 x 12 3 6 x 3 6 12 3 6 13 49 7 0 0 48 Smooth Ceilings 1 2 to 1 13mm to 25mm using CCP or FP escutcheon Beamed Ceilings per NFPA 13 13D or 13R 8 2 4 14 x 14 4 3 x 4 3 14 4 3 13 49 7 0 0 48 16 x 16 4 9 x 4 9 16 4 9 14 53 8 2 0 56 18 x 18 5 5 x 5 5 18 5 5 18 68 1 13 5 0 93 20 x 20 6 1 x 6 1 20 6 1 20 75 7 16 7 1 14 Note Sprinklers shown in Fig 3 and Fig 4 are n...

Page 6: ...nch mm Minimum Spacing Ft m Flow GPM L min Pressure PSI bar Flow GPM L min Pressure PSI bar 12 x 12 3 6 x 3 6 12 3 6 12 45 4 7 5 0 52 12 45 4 7 5 0 52 4 to 6 100 to 152 8 2 4 14 x 14 4 3 x 4 3 14 4 3 14 53 0 10 2 0 71 14 53 0 10 2 0 71 16 x 16 4 9 x 4 9 16 4 9 16 60 6 13 3 0 92 16 60 6 13 3 0 92 16 x 18 4 9 x 5 5 16 4 9 18 68 1 16 8 0 53 18 68 1 16 8 0 53 18 x 18 5 5 x 5 5 18 5 5 19 72 0 18 7 1 29...

Page 7: ...Temp Rating 155 F 68 C Intermediate Temp Rating 175 F 79 C Top of Deflector to Ceiling Inch mm Minimum Spacing Ft m Flow GPM L min Pressure PSI bar Flow GPM L min Pressure PSI bar 12 x 12 3 6 x 3 6 12 3 6 16 60 6 7 6 0 53 16 60 6 7 6 0 53 4 to 6 100 to 152 8 2 4 14 x 14 4 3 x 4 3 14 4 3 18 68 2 9 7 0 69 18 68 2 9 7 0 69 16 x 16 4 9 x 4 9 16 4 9 21 79 5 13 2 0 91 21 79 5 13 2 0 91 16 x 18 4 9 x 5 5...

Page 8: ...del F1 Res 30 LL 49 LL 58 LL Recessed Pendent FP Specifications Sprinklers shall be cULus Listed WaterMark Certified WMCS low flow residential recessed pendent sprinklers engineered to provide a minimum design density of 0 05 gpm ft2 over the listed coverage area Listed flows as specified by the manufacturer s technical data sheets are to be used Residential sprinklers shall be installed in con fo...

Page 9: ...ld head cup with 3 mm glass bulb containing no plas tic parts and having a temperature rating of 155 F 68 C 175 F 79 C Sprinklers shall have a nominal K factor of 4 4 62 8 Standard finish Bronze Chrome plated White Polyester Special finish specify Residential hori zontal sidewall sprinklers shall be Reliable Model F1 Res 44 LL SIN RA3331 Bulletin 033 Model F1 Res 44 LL Recessed Horizontal Sidewall...

Reviews: