5.
Technical Data: F1Res 30 LL CCP Pendent and Recessed Pendent/FP (SIN RA3311)
Thread
Size
Nominal
Orifice
Inch (mm)
Max.
Pressure
psi (bar)
CCP Assembly
Temp. Rating
Max.
Ambient Temp.
K
Factor
Sprinkler
Length
Inch (mm)
°F
°C
°F
°C
½” NPT
(R½)
21
/
64
” (8.2)
175 (12)
135
57
100
38
3.0 (43.2)
2.25 (57)
Max. Coverage area
Ft x Ft (m x m)
Max. Spac-
ing Ft (m)
Ordinary Temp. Rating
(155°F/68°C)
Top of Deflector to Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)
Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3.6 x 3.6)
12 (3.6)
8 (30.3)
7.0 (0.48)
Smooth Ceilings 1/2” to 1”
(13mm to 25mm) using CCP or FP escutcheon
Beamed Ceilings per NFPA 13, 13D, or 13R
8 (2.4)
14 x 14 (4.3 x 4.3)
14 (4.3)
11 (37.8)
13.4 (0.92)
Technical Data: F1Res 49 LL CCP Pendent and Recessed Pendent/FP (SIN RA3316)
Thread
Size
Nominal
Orifice
Inch (mm)
Max.
Pressure
psi (bar)
CCP Assembly
Temp. Rating
Max.
Ambient Temp.
K
Factor
Sprinkler
Length
Inch (mm)
°F
°C
°F
°C
½” NPT
(R½)
7
/
16
” (11)
175 (12)
135
57
100
38
4.9 (70.6)
2.25 (57)
Max. Coverage
area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)
Top of Deflector to Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)
Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3.6 x 3.6)
12 (3.6)
13 (49)
7.0 (0.48)
Smooth Ceilings 1/2” to 1”
(13mm to 25mm) using CCP or FP
escutcheon
Beamed Ceilings per NFPA 13, 13D, or 13R
8 (2.4)
14 x 14 (4.3 x 4.3)
14 (4.3)
13 (49)
7.0 (0.48)
16 x 16 (4.9 x 4.9)
16 (4.9)
14 (53)
8.2 (0.56)
18 x 18 (5.5 x 5.5)
18 (5.5)
18 (68.1)
13.5 (0.93)
20 x 20 (6.1 x 6.1)
20 (6.1)
20 (75.7)
16.7 (1.14)
Note:
Sprinklers shown in Fig. 3 and Fig. 4 are not suitable for installation in ceilings which have positive pressure in
the space above.
Technical Data: F1Res 58 LL CCP Pendent and Recessed Pendent/FP (SIN RA3313)
Thread
Size
Nominal
Orifice
Inch (mm)
Max.
Pressure
psi (bar)
CCP Assembly
Temp. Rating
Max.
Ambient Temp.
K
Factor
Sprinkler
Length
Inch (mm)
°F
°C
°F
°C
½” NPT
(R½)
1
/
2
” (13)
175 (12)
135
57
100
38
5.8 (83.5)
2.25 (57)
Max. Coverage
area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)
Top of Deflector to Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)
Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3.6 x 3.6)
12 (3.6)
16 (61)
7.6 (0.53)
Smooth Ceilings 1/2” to 1”
(13mm to 25mm) using CCP or FP escutcheon
Beamed Ceilings per NFPA 13, 13D, or 13R
8 (2.4)
14 x 14 (4.3 x 4.3)
14 (4.3)
16 (61)
7.6 (0.53)
16 x 16 (4.9 x 4.9)
16 (4.9)
16 (61)
7.6 (0.53)
18 x 18 (5.5 x 5.5)
18 (5.5)
19 (72)
10.8 (0.75)
20 x 20 (6.1 x 6.1)
20 (6.1)
22 (83.3)
14.4 (1.0)