background image

2.

Model F156-300 Extended Coverage Pendent Sprinkler

De

fl

 ector: 

EC

Installation Wrench: 

Model D Sprinkler Wrench

Approval Type: 

Extended Coverage - Light Hazard Occupancy

Model F156-300 Extended Coverage Recessed Pendent Sprinkler

De

fl

 ector: 

EC

Installation Wrench: 

Model GFR2 Sprinkler Wrench

 

Approval Type: 

Extended Coverage - Light Hazard Occupancy

(1)

 When installed directly into a tee, the escutcheon adjustment will be 

reduced.

(2)

 Refer to escutcheon data table for dimensions.

Installation Data:

Nominal 

Ori

fi

 ce

Thread 

Size

“K” Factor

Sprinkler 

Length

Temperature

Rating

Sprinkler

Identi

fi

 cation 

Numbers (SIN)

US

Metric

°F

°C

½” 

(15mm)

½” NPT 

(R1/2)

5.6

80

2.25” 

(57mm)

135
155

57

 68

RA2945

Table 1

Coverage Area

Flow

Rate

Pressure

psi (bar)

Max. Area

Width x Length

gpm L/min K=80 (115) K=5.6 (80)

ft. x ft.

m x m

26
32
40

98.4

125.0
151.4

10.6  (0,7)
17.0  (1,2)
25.0  (1,7)

21.6   (1,5)
34.7   (2,4)
51.0   (3,5)

16 x 16
18 x 18
20 x 20

4.9 x 4.9
5.5 x 5.5

6.0 x 6.0

(1)

(1)

 135°F (57°C) only.

Installation Data

(1)

:

Nominal 

Ori

fi

 ce

Thread

Size

“K” Factor

Sprinkler

Length

Temperature

Rating

Sprinkler

Identi

fi

 cation

Numbers (SIN)

US

Metric

°F

°C

½” 

(15mm)

½” NPT 

(R1/2)

5.6

80

2.25” 

(57mm)

135
155

57
68

RA2945

(1)

 For Coverage Area refer to Table 1.

Model F156-300 EC F1/F2

Model F156-300 EC FP

Fig. 1

Fig. 2