Guarantee

For the Reliable Automatic Sprinkler Co., Inc. guarantee, terms, 
and conditions, visit www.reliablesprinkler.com.

Ordering Information

Specify the following when ordering.

        

Sprinkler

 

•  Model: F1FR56SS Pendent, F1FR56SS Upright, 

 

    F1FR80SS Pendent, F1FR80SS Upright

 

•  Temperature Rating: 135°F (57°C), 155°F (68°C),      

 

    175°F (79°C), 200°F (93°C), 286°F (141°C)

 

•  Threads: NPT or ISO7-1 

              •  Finish: None, White Polyester, Black Polyester
                  Custom Color Polyester

        

Escutcheon (Pendent Only)

 

•  Model: F1 recessed stainless steel, F2 recessed 

                  stainless steel, FP recessed stainless steel, B 
                  stainless steel

      

  Sprinkler Wrench

 

•  Model W2 (pendent, upright)

 

•  Model GFR2 (recessed pendent)

Maintenance

Model F1FR-SS series sprinklers should be inspected and 
the sprinkler system maintained in accordance with NFPA 25. 
Do not clean sprinklers with soap and water, ammonia or any 
other cleaning fluids. Remove dust by gentle vacuuming. Re-
place any sprinkler which has been painted (other than factory 
applied) or damaged in any way. A stock of spare sprinklers 
should be maintained to allow quick replacement of damaged 
or operated sprinklers. Prior to installation, sprinklers should 
be maintained in the original cartons and packaging until used 
to minimize the potential for damage to sprinklers that would 
cause improper operation or non-operation.

Bulletin 065 
December 2019

Page 6 of 6

www.reliablesprinkler.com

Listings and Approvals

• 

Listed by Underwriters Laboratories, Inc. and UL Certified 
for Canada (cULus) - Guide Number VNIV.EX454 - 
Sprinklers, Automatic and Open

• 

FM Approved

P/N 9999970522

Installation

Glass bulb sprinklers have orange bulb protectors to minimize 
bulb damage during shipping, handling, and installation. Reliable 
sprinkler installation wrenches are designed to install sprinklers 
with bulb protectors in place. Remove the bulb protector at the 
time when the sprinkler system is placed in service for fire protec-
tion. Removal of the bulb protector before this time may leave the 
bulb vulnerable to damage. Remove bulb protectors by undoing 
the clasp by hand. Do not use tools to remove bulb protectors. 

Model F1FR-SS series sprinklers must be installed with the Reli-
able sprinkler installation wrench identified in this Bulletin. Any oth-
er wrench may damage the sprinkler. Recommended installation 
torque is 8 to 18 lb/ft (11 to 24 N/m) for 1/2” NPT and ISO7-1R1/2 
sprinklers or 14 to 20 lb/ft (19 to 27 N/m) for 3/4” NPT and ISO7-
1R3/4 sprinklers. Do not tighten sprinklers over the maximum rec-
ommended installation torque. Exceeding the maximum recom-
mended installation torque may cause leakage or impairment of 
the sprinkler. 

Recessed pendent sprinklers are to be installed as shown in Fig. 
2 or Fig 5., as applicable to the specific model being installed. 
Model F1FR-SS series recessed pendent sprinklers may only 
be installed with the Reliable Model F1 stainless steel, Model F2 
stainless steel, or Model FP stainless steel recessed escutcheon. 
The use of any other recessed escutcheon will void all approv-
als and negate all warranties. The Reliable Model FP escutcheon 
may not be used in ceilings having positive pressure with respect 
to the space below. Ensure that the openings in the Model FP 
escutcheon/can assembly are unobstructed following installation. 

Application

Model F1FR-SS series sprinklers are standard spray, quick-re-
sponse sprinklers intended for installation in accordance with 
NFPA 13 and the requirements of applicable Authorities Having 
Jurisdiction. Model F1FR-SS series sprinklers are cULus List-
ed and FM Approved as Corrosion Resistant sprinklers. Verify 
compatibility with the environment where the sprinkler will be 
located prior to installation.

 Wrench                                                                                                                    

Model W2 (upright, pendent)

Model GFR2 (recessed pendent)

(original)

(updated)

Summary of Contents for F1FR-SS Series

Page 1: ...pproved for use with Model F1FR SS series sprinklers Reliable Model B one piece escutcheons are also available All escutcheons listed in this bulletin are manufactured Type 316 stainless steel alloy All Model F1FR SS series sprinklers use a 3 mm glass bulb operating element and beryllium nickel alloy sealing washer gold plated per MIL G 45204 Type 3 Class 2 with PTFE tape on both sides Sprinkler M...

Page 2: ...pproved FP cULus Listed Guards and Shields D 1 Guard cULus FM D 5 Guard Shield cULus FM C 1 Guard FM C 5 Guard Shield FM D 4 Guard Shield FM S 1 Shield cULus FM Finishes None White Polyester Black Polyester Custom Color Polyester Sensitivity Quick response Temperature Rating 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C 286 F 141 C pendent only non recessed Sprinkler Wrench Model W2 pendent Model GF...

Page 3: ... 2 w PTFE tape on both sides Load Screw Type 316 stainless steel Deflector Type 316 stainless steel Cap Type 316 stainless steel Guards and Shields D 1 Guard cULus C 3 Guard Shield cULus FM D 3 Guard Shield cULus C 1 Guard FM Finishes None White Polyester Black Polyester Custom Color Polyester Sensitivity Quick response Temperature Rating 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C 286 F 141 C Spr...

Page 4: ...us Listed FM Approved FP cULus Listed Guards and Shields D 1 Guard cULus D 5 Guard Shield cULus S 2 Shield cULus FM C 1 Guard FM C 5 Guard Shield FM Finishes None White Polyester Black Polyester Custom Color Polyester Sensitivity Quick response Temperature Rating 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C 286 F 141 C pendent only non recessed Sprinkler Wrench Model W2 pendent Model GFR2 recessed ...

Page 5: ... 45204 Type 3 Class 2 w PTFE tape on both sides Load Screw Type 316 stainless steel Deflector Type 316 stainless steel Cap Type 316 stainless steel Guards and Shields C 1 Guard cULus FM C 3 Guard Shield cULus Finishes None White Polyester Black Polyester Custom Color Polyester Sensitivity Quick response Temperature Rating 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C 286 F 141 C Sprinkler Wrench Mod...

Page 6: ...tectors in place Remove the bulb protector at the time when the sprinkler system is placed in service for fire protec tion Removal of the bulb protector before this time may leave the bulb vulnerable to damage Remove bulb protectors by undoing the clasp by hand Do not use tools to remove bulb protectors Model F1FR SS series sprinklers must be installed with the Reli able sprinkler installation wre...