Reliable Automatic Sprinkler Co., Inc.,

 

103 Fairview Park Drive, Elmsford, New York 10523

Bulletin 010 

Rev
.

 G

Bulletin 010 

Rev.

 G

Model HL22 (SIN RA1011) 
K22.4 (320 metric) 
Early Suppression
Fast Response (ESFR) Sprinkler

Features:

1.  cULus, VdS, and LPCB listed as a nominal 

K22.4 (320 metric) ESFR sprinkler.

2.  FM Approved as a quick-response, storage 

and non-storage, sprinkler.

3.  Fusible link operating element.

4. UL Listed Specific Application Criteria to 

Protect Class I - IV commodity and Cartoned 

Unexpanded Group A plastics stored up to 

43 ft (13.1 m) in a 48 ft (14.6 m) building 
(see complete criteria in this Bulletin).

Product Description

The Reliable Model HL22 is an Early Suppression Fast 

Response (ESFR) Sprinkler with a nominal k-factor of 22.4 
(320 metric).  This sprinkler is designed to respond quickly 
to growing fires with a high volume of  water discharge to 
“suppress” rather than “control” fires.

FM Global classifies the Model HL22 as a quick-response 

sprinkler, storage and non-storage, when the sprinkler is 
used in accordance with FM Global Property Loss Preven-
tion Data Sheets.

The Model HL22 sprinkler utilizes a levered fusible alloy 

solder link in either 165°F (74°C) or 212°F (100°C) tempera-
ture ratings. Model HL22 sprinklers are UL Listed for compli-
ance with UL 1767 and have successfully completed high 
clearance tests for rack storage.

Application and Installation

The HL22 ESFR sprinkler is intended for installation in ac-

cordance with NFPA 13 and Factory Mutual (FM) Loss Pre-
vention Data Sheets 2-0 and 8-9, as well as the requirements 
of any Authorities Having Jurisdiction.  See Table 1 for infor-
mation on NFPA and FM Global design criteria for the Model 
HL22 sprinkler.

In addition to design criteria permitted by NFPA 13, the 

Model HL22 also has the following Specific Application List-
ing from UL:
Sprinkler: Model HL22 in 212°F (100°C) only
Maximum Ceiling Height: 48 ft. (14.6 m)
Maximum Storage Height: 43 ft. (13.1 m)
Minimum Aisle Width: 8 ft. (2.44 m)
Permitted Commodities: Class I - IV commodities, encap-
sulated or nonencapsulated, and Cartoned Group A Unex-
panded plastics. Permitted Storage Arrangements: Single- 
and double-row rack storage (no open top containers or 
solid shelves) and palletized and solid pile storage (no open 
top containers or solid shelves).

Minimum System Operating Pressure: 55 psi (3.79 bar).
Installation and Obstruction Criteria: Same as for K25.2 

ESFR sprinklers, but with a maximum deflector to ceiling 
distance of 14 in. (356 mm)

Model HL22 Sprinkler

Installation Criteria

The following general guidelines are provided for infor-

mation only. NFPA and, where applicable, FM Global stan-
dards shall be consulted for complete design and instal-
lation criteria.

Sprinkler Position:

 Pendent, align frame arms with 

the pipe. Deflectors should be parallel with the ceil-
ing or roof.

System Type:

 Wet Pipe Systems Only.

Maximum area of coverage:

 100 ft

2

 (9.3m

2

), greater 

coverage area are allowable in some cases.

Minimum area of coverage:

 64 ft

2

 (5.8m

2

).

Maximum slope ceiling:

 2/12 pitch (9.5°).

Maximum spacing:

 12 ft (3.7m) for building heights

up to 30 ft (9.1m) and 10 feet (3.1m) for building 
heights greater than 30 ft (9.1m), except where other-
wise permitted.

Minimum spacing:

 8 feet (2.4m).

De

fl

 ector distance from walls:

 At least 4 inches 

(102mm) from walls, and no more than one-half the 
allowable distance permitted between sprinklers.

De

fl

 ector to Top of Storage:

 At least 36in (914mm).

De

fl

 ector to ceiling Distance:

 6-18 in (152-457mm) 

per NFPA 13; 6-14 in (152-356mm) when using UL 
Listed Special Application criteria for ceilings up to 
48 ft (14.6m).

Center Line of Thermal Sensing
Element To Ceiling Distance (FM Only):

 Max. 17 in 

(425mm); Min. 2 in (50mm) with smooth ceilings; Min. 
4 in (100mm) with non-smooth ceilings. 

Summary of Contents for HL22

Page 1: ...lso has the following Specific Application List ing from UL Sprinkler Model HL22 in 212 F 100 C only Maximum Ceiling Height 48 ft 14 6 m Maximum Storage Height 43 ft 13 1 m Minimum Aisle Width 8 ft 2 44 m Permitted Commodities Class I IV commodities encap sulated or nonencapsulated and Cartoned Group A Unex panded plastics Permitted Storage Arrangements Single and double row rack storage no open t...

Page 2: ...ve a UL Listed Specific Application criteria permitting single and double row rack storage no open top containers or solid shelves and palletized and solid pile storage no open top contain ers or solid shelves of Class I IV commodities encapsulat ed or nonencapsulated and cartoned Group A unexpand ed plastics stored up to 43 ft 13 1m under ceilings up to 48 ft 14 6m high when installed with 8 ft a...

Page 3: ...prinkler wrench for re moval and installation Any other type of wrench may damage the sprinkler Ordering Information Specify 1 Sprinkler Model HL22 2 Temperature Rating 165 F 74 C 212 F 100 C 3 Thread Type 1 in NPT ISO 7 R1 3 ...

Page 4: ...roughout the United States Canada and foreign countries Automatic sprinklers Flush automatic sprinklers Recessed automatic sprinklers Concealed automatic sprinklers Adjustable automatic sprinklers Dry automatic sprinklers Intermediate level sprinklers Open sprinklers Spray nozzles Alarm valves Retarding chambers Dry pipe valves Accelerators for dry pipe valves Mechanical sprinkler alarms Electrica...

Reviews: