Listings and Approvals

1.  Listed by Underwriters Laboratories, Inc. and UL 

certified for Canada (cULus). 

2.  FM Approved as a quick-response, storage and non-

storage, sprinkler (FM).

3.  VdS Schadenverhütung (VdS).
4.  Loss Prevention Certification Board (LPCB).

Patents

Covered by one or more of the following patents:
US Patent No. 6,502,643
US Patent No. 6,868,917
AU Patent No. 722593
GB Patent No. 233677

Maintenance

The HL22 Sprinkler should be inspected and the sprin-

kler system maintained in accordance with NFPA 25.  Do 
not clean sprinklers with soap and water, ammonia or any 
other cleaning fluids.  Remove dust by using a soft brush 
or gentle vacuuming.  Replace any sprinkler that has been 
painted (other than factory applied) or damaged in any 
way.  A stock of spare sprinklers should be maintained to 
allow quick replacement of damaged or operated sprin-
klers.  Prior to installation, sprinklers should be maintained 
in the original cartons and packaging until used.  This will 
minimize the potential for damage to sprinklers that would 
cause improper operation or non-operation.

Engineering Speci

fi

 cation 

Model HL22 ESFR 

Sprinklers shall be Early Suppression Fast Response 

(ESFR) pendent suppression mode sprinklers cULus Listed 
and FM, VdS, and LPCB Approved for commodity storage 
applications.  Sprinkler frame and deflector to be of bronze 
construction with deflector located inside of the frame arms. 
Sprinkler shall have a maximum listed/approved ceiling-to-
deflector distance of 18”. [Sprinklers shall have a UL Listed 
Specific Application criteria permitting single- and double-
row rack storage (no open top containers or solid shelves) 
and palletized and solid pile storage (no open top contain-
ers or solid shelves) of Class I-IV commodities encapsulat-
ed or nonencapsulated and cartoned Group A unexpand-
ed plastics stored up to 43 ft (13.1m) under ceilings up to 
48 ft (14.6m) high when installed with 8 ft. aisles, a minimum 
operating pressure of 55 psi (3.79 bar), a maximum deflec-
tor to ceiling distance of 14 in (356mm), and a temperature 
rating of 212°F (100°C).]

Fusible alloy solder link assembly shall utilize the strut and 

lever principle of operation with approved fast response 
beryllium-nickel thermal element with protective [black 
painted (165°F)] [white painted (212°F)] coating. Water 
seal shall consist of a Teflon-coated Belleville spring washer 
and brass cap assembly containing no plastic parts.  ESFR 
sprinklers shall have a nominal K-factor of 22.4 and [1 in 
NPT][ISO 7-R1] threaded end connections.  Sprinkler tem-
perature rating shall be [Ordinary 165°F (74°C)] [Intermedi-
ate 212°F (100°C)].  ESFR pendent sprinklers shall be Reli-
able Model HL22, SIN RA1011 (Bulletin 010).

Model HL22 Temperature Ratings and Approvals

Temperature

Classi

fi

 cation

Temperature 

Rating

Link

Color

Frame

Color

Maximum Ambient

Temperature

Approvals

Sprinkler 

Identi

fi

 cation 

Number

(SIN)

°F

°C

°F

°C

Ordinary

165

74

Black

Uncolored

100

38

cULus, FM, VdS, LPCB

RA1011

Intermediate

212

100

White

White

150

66

cULus & UL Spec App, FM, VdS, 

LPCB

RA1011

Installation Data

Sprinkler Type

Nominal Ori

fi

 ce

Thread Size

Nominal K-Factor

Maximum Working

Pressure

US

Metric

Pendent

0.87” 

(22.1mm)

1” NPT

ISO 7-R1 (Optional)

22.4

320

175 psi

(12.1 bar)

2.

Summary of Contents for HL22

Page 1: ...lso has the following Specific Application List ing from UL Sprinkler Model HL22 in 212 F 100 C only Maximum Ceiling Height 48 ft 14 6 m Maximum Storage Height 43 ft 13 1 m Minimum Aisle Width 8 ft 2 44 m Permitted Commodities Class I IV commodities encap sulated or nonencapsulated and Cartoned Group A Unex panded plastics Permitted Storage Arrangements Single and double row rack storage no open t...

Page 2: ...ve a UL Listed Specific Application criteria permitting single and double row rack storage no open top containers or solid shelves and palletized and solid pile storage no open top contain ers or solid shelves of Class I IV commodities encapsulat ed or nonencapsulated and cartoned Group A unexpand ed plastics stored up to 43 ft 13 1m under ceilings up to 48 ft 14 6m high when installed with 8 ft a...

Page 3: ...prinkler wrench for re moval and installation Any other type of wrench may damage the sprinkler Ordering Information Specify 1 Sprinkler Model HL22 2 Temperature Rating 165 F 74 C 212 F 100 C 3 Thread Type 1 in NPT ISO 7 R1 3 ...

Page 4: ...roughout the United States Canada and foreign countries Automatic sprinklers Flush automatic sprinklers Recessed automatic sprinklers Concealed automatic sprinklers Adjustable automatic sprinklers Dry automatic sprinklers Intermediate level sprinklers Open sprinklers Spray nozzles Alarm valves Retarding chambers Dry pipe valves Accelerators for dry pipe valves Mechanical sprinkler alarms Electrica...

Reviews: