4. If start/stop control is remote, remove the factoryinstalled jumper
between terminals TB235 and TB2132. See Figure 36. With the
operator's start/stop controls mounted remotely from the controller,
the AC fused disconnect or circuit breaker must be mounted in
close proximity to the operator controls.
WARNING
WHEN THE START/STOP SWITCH DOES NOT INCLUDE AN AC POWER DIS
CONNECT FUNCTION IN THE STOP POSITION, THE AC POWER DISCON
NECT SWITCH MUST BE MOUNTED IN CLOSE PROXIMITY TO THE OPERA
TOR'S START/STOP CONTROLS. THIS IS REQUIRED AS THE DC2 DRIVE
DOES NOT HAVE AN ARMATURE LOOP CONTACTOR. A SINGLE FAULT LIKE
A THYRISTOR SHORT MAY CAUSE MOTOR ROTATION WHEN IN THE STOP
MODE. FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN BODILY
INJURY.
START/STOP
PUSHBUTTON
CONTACT
FOLLOWER
38
35
132
1
TB2
STOP
START
38
35
132
1
TB2
START/STOP
CONTACT
2
1
2
Remove the Jumper between
TB235 and TB2132 if a Remote
Start/Stop Device is used.
Start = Closed
Stop = Open
Figure 36. Start/Stop Circuit Connection.