Danger
It is forbidden to store, even temporarily, combustible products
and substances in or near the boiler.
Caution
The boiler must be installed in a frost-free area.
The boiler must have an earthed electrical connection.
A connection to the drain must be present for the condensate
drain close to the boiler.
A technical clearance of at least 1100 mm is required at the
front (service side) of the boiler. We recommend a clearance of
at least 500 mm above the boiler.
Caution
If the power supply cable is permanently connected, you must
always install a main bipolar switch with an opening gap of at least
3 mm (BS EN 60335-1).
5.3
Transport
The boiler is supplied fully assembled and packaged on a pallet. Without
the packaging, the boiler will fit through all standard doorways.
The boiler is equipped with integrated transport wheels, meaning it can
easily be moved.
Fig.17
Boiler package
AD-0001164-01
1200
1835
800