6.5.3
Dimensions of flue gas outlet pipe
Warning
The pipes connected to the flue gas adapter must satisfy the
following dimension requirements.
d
1
External dimensions of flue gas outlet pipe
Tab.20 Dimensions of pipe
d
1
(min-max)
150 mm
149 - 151 mm
200 mm
199 - 201 mm
d
1
External dimensions of flue gas outlet pipe
D
1
External dimensions of air supply pipe
Tab.21 Dimensions of pipe
d
1
(min-max)
D
1
(min-max)
150/150 mm 149 - 151 mm
149 - 151 mm
6.5.4
Length of the air and flue gas pipes
The maximum length of the flue gas outlet and air supply channel vary
depending on the appliance type; consult the relevant chapter for the
correct lengths.
Important
When using bends, the maximum chimney length (L) must be
shortened according to the reduction table.
For adaptation to another diameter use approved transitions
The boiler is also suitable for longer chimney lengths and
diameters other than those specified in the tables. Contact us
for more information.
Room-ventilated model (B
23P
)
L Length of the flue gas outlet channel to roof feed-through
Flue gas outlet
Air supply
With a room-ventilated version, the air supply opening stays open; only the
flue gas outlet opening is connected. This will ensure that the boiler
obtains the necessary combustion air directly from the installation area.
Use adapters when using air supply and flue gas discharge pipes with
diameters other than the standard 150 or 200 mm.
Fig.25
Dimensions of open connection
AD-3001094-01
ød
1
Fig.26
Dimensions of parallel connection
AD-3000963-01
ød
1
øD
1
Fig.27
Room-ventilated version
AD-0001169-01
L =
6 Installation
7665063 - v.05 - 18102018