9.3.3
Counters - FSB-WHB-HE-150-300
Tab.39
> FSB-WHB-HE-150-300 - Counters at user level
Code
Description
Range
AC001
Number of hours that the appliance has been on mains power
0 Hours - 65534 Hours
DC002
Numbers of Domestic Hot Water diverting valve cycles
0 - 4294967295
DC003
Number of hours during which the diverting valve is in DHW position
0 Hours - 4294967295 Hours
DC004
Number of burner starts for Domestic Hot Water
0 - 4294967295
DC005
Number of burning hours in Domestic Hot Water
0 Hours - 4294967295 Hours
PC003
Total number of burning hours. For heating and domestic hot water
0 Hours - 65534 Hours
Tab.40
> FSB-WHB-HE-150-300 - Counters at installer level
Code
Description
Range
DC001
Total power consumption used by Domestic Hot Water
0 kW - 4294967295 kW
PC002
Total number of burner starts. For heating and domestic hot water
0 - 65534
PC004
Number of burner flame loss
0 - 65534
9.3.4
Signals - FSB-WHB-HE-150-300
Tab.41
> FSB-WHB-HE-150-300 - Signals at user level
Code
Description
Range
AM001
Is the appliance currently in domestic hot water production mode?
0 = Off
1 = On
AM010
The current pump speed
0 % - 100 %
AM012
Current main status of the appliance.
DeviceState
AM014
Current sub status of the appliance.
DeviceSubStatus
AM015
Is the pump running?
0 = Inactive
1 = Active
AM016
Flow temperature of appliance.
-25 °C - 150 °C
AM017
The temperature of heat exchanger
-25 °C - 150 °C
AM018
Return temperature of appliance. The temperature of the water
entering the appliance.
-25 °C - 150 °C
AM019
Water pressure of the primary circuit.
0 bar - 25.5 bar
AM022
On / Off heat demand
0 = Off
1 = On
AM024
Actual relative power of the appliance
0 % - 655.35 %
AM027
Instantaneous outside temperature
-60 °C - 60 °C
AM028
Value of the 0 to 10 Volt input. Meaning is dependant on the current
input function setting.
0 V - 25 V
AM037
Status of the three way valve
0 = CH
1 = DHW
AM040
Temperature used for hot water control algorithms.
-25 °C - 150 °C
AM101
Internal system flow temperature setpoint
0 °C - 120 °C
AP078
Outside sensor detected in the application
0 = No
1 = Yes
GM001
Actual fan RPM
0 Rpm - 8500 Rpm
GM002
Actual fan RPM setpoint
0 Rpm - 8500 Rpm
GM006
Gas Pressure Switch status
0 = Open
1 = Closed
2 = Off
GM008
Actual flame current measured
0 µA - 25 µA
9 Settings
58
7665063 - v.05 - 18102018