Gas 220 Ace
160
200
250
300
B1 boiler
No
No
No
No
Cogeneration space heater
No
No
No
No
Combination heater
No
No
No
No
Rated heat output
Prated
kW
152
194
243
291
Useful heat output at nominal heat out
put and high temperature operation
P
4
kW
152.1
194.4
243.3
290.9
Useful heat output at 30% of rated heat
output and low temperature regime
P
1
kW
50.8
64.8
81.2
97.2
Seasonal space heating energy efficiency
ƞ
s
%
-
-
-
-
Useful efficiency at rated heat output
and high temperature regime
ƞ
4
%
87.8
87.6
87.7
87.7
Useful heat output at 30% of rated heat
output and low temperature regime
ƞ
1
%
97.8
97.3
97.5
97.7
Auxiliary electricity consumption
Full load
elmax
kW
0.275
0.204
0.323
0.343
Part load
elmin
kW
0.047
0.057
0.057
0.048
Standby mode
P
SB
kW
0.005
0.011
0.011
0.009
Other items
Standby heat loss
P
stby
kW
0.191
0.267
0.267
0.267
Ignition burner power consumption
P
ign
kW
-
-
-
-
Annual energy consumption
Q
HE
kWh
GJ
-
-
-
-
Sound power level, indoors
L
WA
dB
67
68
72
72
Emissions of nitrogen oxides
NO
X
mg/kWh
35
40
45
50
(1) Low temperature means 30 °C for condensing boilers, 37 °C for low temperature boilers and 50 °C (at heater inlet) for other heating
appliances.
(2) High temperature operation means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet.
See
Refer to the back cover for contact details.
3 Technical specifications
7665063 - v.05 - 18102018
15