background image

Heat of condensation

The energy transferred from  
the condenser to the air is  
composed of:

1.  Heat energy extracted from the 

evaporator.

2. Electrical drive power.
3.  The heat of condensation re-

leased through the condensation 
of water vapour. 

For the change from a liquid to 
a gaseous state, energy is neces-
sary. This energy is termed heat of 
evaporation. It does not cause any 
rise of temperature, it is only nec-
essary for the change from a liquid 
to a gaseous state. Vice versa, 

energy is released during the liq-
uefaction of gas, which is termed 
heat of condensation. 
The amount of heat of evaporation 
and condensation is the same.   

For water, this is:  
2250 kJ/kg (.18 kJ = 1kcal)

This shows that a relatively large 
amount of energy is released 
through the condensation of water 
vapour.

If the moisture to be condensed is 
not introduced through evapora-
tion in the room itself, but from 
outside, e.g. via ventilation, the 
heat of condensation released in 
the process contributes towards 
room heating. In drying processes, 

the heat energy is recirculated, 
which is consumed during evapo-
ration and released during con-
densation. The supplied air during 
dehumidification creates a large 
amount of heat energy, which is 
expressed as a rise of temperature. 

The time necessary for drying 
normally does not depend only on 
the unit capacity, but is rather de-
termined by the rate at which the 
material or parts of the building 
release their moisture.

 

Safety Instructions

The units were subjected to ex-
tensive material, functional and 
quality inspections and tests prior 
to delivery.
The unit can however constitute 
a hazard if used improperly by 
untrained persons or not for the 
intended purpose.
The following information must be 
observed:

 

The units must not be installed 
or operated in locations subject 
to explosion hazards

 

The units must not be installed 
and operated in oil, sulphur, 
chlorine or salt containing at-
mospheres

 

The units must be installed up-
right and stable

 

The units must not be subjected 
to a direct jet of water

 

The air inlet and outlet must 
always be kept free

 

The intake guard grilles must 
always be free of dirt and loose 
objects

 

The units must not be covered 
during operation

 

Never insert objects in the unit

 

The units must not be trans-
ported during operation

 

The units must only be trans-
ported with drained condensate 
containers and dry evaporator

   All electric cables outside the 

units must be protected against 
damage (e.g. due to animals)

 

The condensate containers 
must be drained prior to each 
change of location

CAuTIOn

Only specially authorised firms 
may carry out work on the re-
frigeration system and electri-
cal equipment. 

CAuTIOn

Extension of the connecting 
cable may only be carried 
out by authorised electricians 
taking into account the unit 
power consumption, cable 
length and local use.

REMKO AMT

Summary of Contents for AMT 110-E

Page 1: ...Edition GB R12 REMKO AMT Dehumidifier Operation Technology Spare Parts...

Page 2: ......

Page 3: ...xcepted Dehumidification 4 Safety Instruction 6 Proper use 7 Customer Service and Warranty 7 Environmental Protection and Recycling 7 Equipment Description 8 Installation 9 Commissioning 10 Shutdown 1...

Page 4: ...rom buildings or materials is absorbed by the ambient air This increases their moisture content and ultimately results in corrosion mould rot peeling of paint coat ings and other unwanted moisture dam...

Page 5: ...fall below Building material and structures can absorb considerable amounts of water e g bricks 90 190 l m heavy concrete 140 190 l m sand lime bricks 180 270 l m The drying of moist materials e g ma...

Page 6: ...capacity but is rather de termined by the rate at which the material or parts of the building release their moisture Safety Instructions The units were subjected to ex tensive material functional and...

Page 7: ...on a wooden pallet if necessary The packaging materials are en vironmentally friendly and can be recycled With the reuse of packaging mate rial you make a valuable contribu tion to the reduction of w...

Page 8: ...makes dehumidifiers particu larly economical in operation At the condenser heat exchang er the cooled and dehumidified air is reheated and blown back into the room via the air outlet The conditioned...

Page 9: ...Room air circulation can be improved by installing the units raised about 1 metre The room to be dried or dehu midified must be closed with respect to the ambient atmos phere Open windows doors etc as...

Page 10: ...nel 1 2 3 4 1 Operating hour counter 2 Operating switch with pilot light 3 YELLOW Pilot light Container full 4 RED Pilot light Fault Overheating Operation with a hygrostat The REMKO hygrostat accessor...

Page 11: ...er drips steadily or only during the defrost phases in the condensate trap or condensate container Via a connection not with AMT 40 E and 110 E the condensate flows into the condensate con tainer loca...

Page 12: ...ant C The water flows via a hose into a lower located drain This variant enables unsupervised continuous duty Condensate drain AMT 110 E AMT 110 E units are not provided with an internal condensate co...

Page 13: ...d protective handle This can easily be removed if required The following must be observed for unit transport 1 Prior to a change of location switch off the unit and discon nect the mains plug from the...

Page 14: ...tor for pos sible icing frost formation If this is the case the automatic defrost function and tempera ture sensor must be checked If the unit does not operate cor rectly despite the checks carried ou...

Page 15: ...PE Steuerplatine C1 S C R PE NTC NTC Rot Gelb SW M1 M2 COMP FANMOTOR S1 AMT 40 E AMT 55 E to 110 E Electrical wiring diagram Test NTC NTC Rot only AMT 110 E T T T Test button The test button is only i...

Page 16: ...hanges in dimensions and design in the interest of technical advances Exploded view AMT 40 E 4 5 6 8 10 11 12 13 14 15 2 1 16 17 20 21 26 27 22 25 25 30 29 32 33 35 34 38 37 36 39 40 45 46 47 49 50 23...

Page 17: ...plate 1105620 23 Wheelaxle 1105621 24 Rubber stopper supporting stand set 1105622 25 Wheel 1102155 26 Wheel cap 1101623 27 Circlip 1101622 29 Pull relief 1101267 30 Mains cable with plug 1105624 31 I...

Page 18: ...s in dimensions and design in the interest of technical advances Exploded view AMT 55 E 80 E 3 6 7 8 2 1 5 10 11 12 13 14 15 16 17 20 21 22 25 25 23 18 29 30 31 40 35 39 37 36 50 51 48 52 49 47 46 45...

Page 19: ...ion complete 1105646 1105671 21 End cover 1105647 1105647 22 Base plate 1105648 1105672 23 Wheelaxle 1105649 1105673 24 Rubber stopper base plate set 1105622 1105622 25 Wheel 1102155 1102155 26 Wheel...

Page 20: ...e changes in dimensions and design in the interest of technical advances Exploded view AMT 110 E 3 2 1 16 17 18 19 10 5 4 6 7 8 9 11 15 24 25 22 20 26 29 27 31 35 29 30 47 46 44 43 42 37 41 38 40 39 2...

Page 21: ...19 Solenoid valve 1105669 20 Coil for solenoid valve 1105614 22 Compressor complete 1105688 24 Housing part inspection complete 1105689 25 End cover 1105690 26 Base plate 1105691 27 Wheelaxle 1105692...

Page 22: ...18 Date Signature 19 Date Signature 20 Date Signature Remarks Model Model No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Clean unit surface Clean unit interior Clean fan blade Clean fan housin...

Page 23: ...tating piston Rotating piston Refrigerant R134a R407c R407c R407c Refrigerant quantity kg 0 31 0 55 0 65 1 55 Voltage supply V Hz 230 1 50 Max rated power consumption A 3 9 4 0 4 9 7 2 Max power consu...

Page 24: ...eing more than just a good reliable supplier REMKO a partner that helps solve problems Sales REMKO not only provides an extensive sales network in Germany and abroad but also unusually highly qualifie...

Reviews: