background image

Starting the unit

1.   Move the operating 

switch [2] to the "0" 
(off) position.

2.   Connect 

the unit's power 
plug to a properly 
installed and 
fused mains 
socket.  

230V/50 Hz  

3.   Move the operating 

switch [2]to the "I"  
(on) position.

The green indicator light 
on the switch [2] illuminates.
The units switch on with a time 
delay of around 10 seconds and 
then run in permanent operating 
mode.

Before commissioning the unit or if 
local requirements dictate, the air-
inlet grille and air-outlet grille must 
be checked for contamination.

Important notes prior 
to commissioning 

   All extensions to the electrical 

connection must be of 
a sufficient cable size and must 
only be used fully rolled out or 
unrolled

   Never use the power supply 

connection cable as a pull cord 

   After being switched on, 

the units operate fully-
automatically until switched 
off by the float when 
the condensate container is full 
(not AMT 115-E)

   The condensate container must 

be inserted properly 

   In order to prevent damage 

to the condenser, the units are 
equipped with a mechanism 
that prevents the compressor 
from being immediately 
switched back on after it is 
switched off 

The compressor does not 
switch back on until after 
a waiting time of around one 
minute!

Commissioning

Control panel

1

2

3

4

1  =  Operating hours counter
2  =   Operating switch with 

"Indicator light"

3  =   -YELLOW- indicator light 

"Container full"

4  =   -RED- indicator light 

„Malfunction / overheating"

Operation with a humidity 
switch

The REMKO humidity switch 
(accessories) is supplied with 
a special adapter.  
The following procedure must 
be followed when commissioning 
units in conjunction with 
a humidity switch:
1.  Insert the adapter 

into a properly fused mains 
socket.

2.  Place the humidity 

switch in a suitable 
location within the room 
being dehumidified. 
Not in the immediate vicinity of 
the units or sources of heat.

3.  Insert the power plug (or a cable 

extension) into the adapter.

4.  Set the desired air humidity 

on the humidity switch.

5.  Move the operating switch [2] 

on the unit to position "I".

The units will switch on 
automatically when the air humidity 
in the room exceeds the pre-set level 
on the humidity switch. 

 
The units will now operate fully-
automatically until the desired 
relative humidity (% RH) has been 
reached or until the unit is 
switched off by the float when 
the condensate container is full 
(not AMT 115-E). In the event 
that this occurs, the yellow 
"Container full"

 indicator light will 

illuminate.

NOTE

A contaminated grille or filter 
must be cleaned or replaced 
immediately.

NOTE

In room temperatures below 

10°C

 and relative humidity 

below 

40%

, economical use 

of the unit can no longer be 
guaranteed.

10

REMKO AMT

Summary of Contents for AMT 115-E

Page 1: ...Edition GB D09 REMKO AMT Air dehumidifiers Operation Technology Spare parts REMKO AMT 45 E to 115 E...

Page 2: ......

Page 3: ...ts Air dehumidification 4 Safety notes 6 Intended use 7 Customer service and guarantee 7 Environmental protection and recycling 7 Unit description 8 Set up 9 Commissioning 10 Shutdown 12 Transportatio...

Page 4: ...isture water vapour released from parts of a building or materials is absorbed by the surrounding air As a result the moisture content increases which ultimately gives rise to corrosion mould rot peel...

Page 5: ...the dew point making it easier for the temperature to fall below it Building materials and structures are capable of absorbing considerable volumes of water such as brick 90 190 l m heavy concrete 140...

Page 6: ...quality inspections prior to delivery However dangers can result from the units if they are used improperly or not as intended by untrained personnel The following notes must be observed in full The...

Page 7: ...on a wooden pallet The packaging materials are environmentally friendly and can be recycled By recycling packaging materials you make a valuable contribution to the reduction of waste and conservation...

Page 8: ...d enough for rime formation to occur rendering defrosting unnecessary Therefore the air dehumidifiers work economically The cooled and dehumidified air is re heated by the condenser heat exchanger and...

Page 9: ...osed to the neighbouring atmosphere Air circulation is improved if the unit is set up approx 1 m above the ground Avoid having opened windows and doors etc and avoid frequent entry to or exit from the...

Page 10: ...mmissioning Control panel 1 2 3 4 1 Operating hours counter 2 Operating switch with Indicator light 3 YELLOW indicator light Container full 4 RED indicator light Malfunction overheating Operation with...

Page 11: ...tainer either continuously or only during the defrosting phases The condensate is fed into the condensate container below via a connection nozzle not AMT 45 E and AMT 115 E A float is located inside t...

Page 12: ...is fed into a lower drain via a hose pipe This variant enables unattended permanent operating mode AMT 115 E condensate drain Due to their high dehumidification capacity the AMT 115 E units are not eq...

Page 13: ...tion and protective clamp This can also be dismantled easily if required When transporting the units observe the following 1 Before each change of location switch off the unit and remove the power plu...

Page 14: ...ry Check the evaporator for ice or rime formation If ice has formed check the functionality of the automatic defrost and the temperature sensor If the unit fails to function correctly after the checks...

Page 15: ...riebs stunden F 3 15 A 1 0 A 2 1 4 3 2 1 4 3 Kondensatpumpe optional SCHWARZ WEISS VIOLETT VIOLETT Steckdose am Ger t Stecker F hler C Verdampfer Kondensator F hler Wasser Stop Lampe St rung Lampe Was...

Page 16: ...ions and design as part of the ongoing technical development process Exploded view of the AMT 45 E unit 4 5 6 8 10 11 12 13 14 15 2 1 16 17 20 21 26 27 22 25 25 30 29 32 33 35 34 38 37 36 39 40 45 46...

Page 17: ...909 18 Operating condenser 1105910 20 Inspection housing part cpl 1105618 21 Completion panel 1105619 22 Base plate 1105956 23 Axle 1105621 24 Base plate rubber stop set 1105622 25 Wheel 1102155 26 Hu...

Page 18: ...design as part of the ongoing technical development process Exploded view of the AMT 65 E and 85 E units 3 6 7 8 2 1 5 10 11 12 13 14 15 16 17 20 21 22 25 25 23 18 29 30 31 40 35 39 37 36 50 51 48 52...

Page 19: ...t cpl 1105671 1105671 21 Completion panel 1105647 1105647 22 Base plate 1105957 1105957 23 Axle 1105673 1105673 24 Base plate rubber stop set 1105622 1105622 25 Wheel 1102155 1102155 26 Hubcap 1101623...

Page 20: ...ensions and design as part of the ongoing technical development process Exploded view of the AMT 115 E unit 3 2 1 16 17 18 19 10 5 4 6 7 8 9 11 15 24 25 22 20 26 29 27 31 35 29 30 47 46 44 43 42 37 41...

Page 21: ...enoid valve 1105715 20 Coil for solenoid valve 1105714 22 Compressor cpl 1105746 24 Inspection housing part cpl 1105689 25 Completion panel 1105690 26 Base plate 1105951 27 Axle 1105692 28 Base plate...

Page 22: ...te Signature 19 Date Signature 20 Date Signature Comments Unit type Unit number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Unit cleaned outside Unit cleaned inside Fan blade cleaned Fan housin...

Page 23: ...Refrigerant quantity g 480 580 750 1270 Power supply V Hz 230 1 50 Max rated current consumption A 3 2 4 0 4 8 6 7 Max power consumption kW 0 730 0 890 1 020 1 385 at 20 C 70 RH kW 0 510 0 640 0 740...

Page 24: ...ust be advisers to our customers in air conditioning and heating technology Customer service Our units operate precisely and reliably However in the event of a malfunction REMKO customer service is qu...

Reviews: