Starting the unit
1. Move the operating
switch [2] to the "0"
(off) position.
2. Connect
the unit's power
plug to a properly
installed and
fused mains
socket.
230V/50 Hz
3. Move the operating
switch [2]to the "I"
(on) position.
The green indicator light
on the switch [2] illuminates.
The units switch on with a time
delay of around 10 seconds and
then run in permanent operating
mode.
Before commissioning the unit or if
local requirements dictate, the air-
inlet grille and air-outlet grille must
be checked for contamination.
Important notes prior
to commissioning
■
All extensions to the electrical
connection must be of
a sufficient cable size and must
only be used fully rolled out or
unrolled
■
Never use the power supply
connection cable as a pull cord
■
After being switched on,
the units operate fully-
automatically until switched
off by the float when
the condensate container is full
(not AMT 115-E)
■
The condensate container must
be inserted properly
■
In order to prevent damage
to the condenser, the units are
equipped with a mechanism
that prevents the compressor
from being immediately
switched back on after it is
switched off
The compressor does not
switch back on until after
a waiting time of around one
minute!
Commissioning
Control panel
1
2
3
4
1 = Operating hours counter
2 = Operating switch with
"Indicator light"
3 = -YELLOW- indicator light
"Container full"
4 = -RED- indicator light
„Malfunction / overheating"
Operation with a humidity
switch
The REMKO humidity switch
(accessories) is supplied with
a special adapter.
The following procedure must
be followed when commissioning
units in conjunction with
a humidity switch:
1. Insert the adapter
into a properly fused mains
socket.
2. Place the humidity
switch in a suitable
location within the room
being dehumidified.
Not in the immediate vicinity of
the units or sources of heat.
3. Insert the power plug (or a cable
extension) into the adapter.
4. Set the desired air humidity
on the humidity switch.
5. Move the operating switch [2]
on the unit to position "I".
The units will switch on
automatically when the air humidity
in the room exceeds the pre-set level
on the humidity switch.
The units will now operate fully-
automatically until the desired
relative humidity (% RH) has been
reached or until the unit is
switched off by the float when
the condensate container is full
(not AMT 115-E). In the event
that this occurs, the yellow
"Container full"
indicator light will
illuminate.
NOTE
A contaminated grille or filter
must be cleaned or replaced
immediately.
NOTE
In room temperatures below
10°C
and relative humidity
below
40%
, economical use
of the unit can no longer be
guaranteed.
10
REMKO AMT
Summary of Contents for AMT 115-E
Page 2: ......